Worked example
Example: 2000 m3/d, no nitrification. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Wastewater flow | 2,000.0 m³/d |
| Influent BOD₅ | 300.00 mg/L |
| Effluent soluble BOD₅ | 10.000 mg/L |
| BOD₅/BOD_u ratio | 68.000 % |
| Biomass wasted (as VSS) | 180.00 kg/d |
| Ammonia nitrogen nitrified (0 if none) | 0 mg/L |
Applying the formula below gives:
| Result | Value |
|---|---|
| Oxygen required | 597.34 kg/d |
| Air at 23.2 % O₂ by mass, 1.2 kg/m³, if all oxygen transferred | 89.401 m³/h |
Open this example in the calculator and change any input.
Formula
\(\dot m_{O_2} = \frac{Q(S_0 - S)}{f} - 1.42P_x + 4.57\,Q\,\Delta N\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q\) | Wastewater flow | m³/s |
| \(S_0\) | Influent BOD₅ | kg/m³ |
| \(S\) | Effluent soluble BOD₅ | kg/m³ |
| \(f\) | BOD₅/BOD_u ratio | - |
| \(P_x\) | Biomass wasted (as VSS) | kg/s |
| \(\Delta N\) | Ammonia nitrogen nitrified (0 if none) | kg/m³ |
| \(\dot m_{O_2}\) | Oxygen required | kg/s |
| \(\dot V_a\) | Air at 23.2 % O₂ by mass, 1.2 kg/m³, if all oxygen transferred | m³/s |
Method and standards
Oxygen balance.
Where it is used
- ETP blower sizing.
- Operator examinations.
Common mistakes
- Total instead of soluble effluent BOD.
- Forgetting nitrification.
Assumptions and limits
- Steady state.
- A negative oxygen balance (biomass wasted too large for the BOD removed) is shown as zero and flagged as inconsistent inputs.
References
- O₂ = Q(S₀ − S)/f − 1.42 P_x + 4.57 Q ΔN (Metcalf & Eddy, Wastewater Engineering)
Questions and answers
2000 m³/d, 300 → 10 mg/L BOD, f 0.68, 180 kg/d wasted?
About 597 kg O₂ a day.
Why subtract 1.42 P_x?
Oxygen bound in the wasted biomass is not consumed.
Nitrification?
Adds 4.57 kg O₂ per kg of ammonia nitrogen oxidised.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.