Worked example
Example: 200 L from 25 to 60 °C in 1 h, 95 %; 3 kW heater. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Volume of water | 200.00 L |
| Starting temperature | 25.000 °C |
| Final temperature | 60.000 °C |
| Time allowed | 60.000 min |
| Heater efficiency (heat into the water) | 95.000 % |
| Heater available (to find the time) | 3.0000 kW |
Applying the formula below gives:
| Result | Value |
|---|---|
| Mass of water | 199.41 kg |
| Heat needed | 8.1034 kWh |
| Electrical energy used | 8.5299 kWh |
| Heater power for the time allowed | 8.5299 kW |
| Heating time with the heater available | 170.60 min |
Open this example in the calculator and change any input.
Formula
\(Q = m\,(h_2 - h_1) \approx m\, c_p\, \Delta T, \quad P = \frac{Q}{\eta\, t}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V\) | Volume of water | m³ |
| \(T_1\) | Starting temperature | K |
| \(T_2\) | Final temperature | K |
| \(t\) | Time allowed | s |
| \(\eta\) | Heater efficiency (heat into the water) | - |
| \(P_a\) | Heater available (to find the time) | W |
| \(m\) | Mass of water | kg |
| \(Q\) | Heat needed | J |
| \(E\) | Electrical energy used | J |
| \(P\) | Heater power for the time allowed | W |
| \(t_h\) | Heating time with the heater available | s |
Method and standards
Energy balance on the water with IF97 enthalpies.
Where it is used
- Geysers, calorifiers and process tanks.
- Checking immersion heaters.
Common mistakes
- Forgetting efficiency and losses.
- Using litres as kg at high temperature.
Assumptions and limits
- Open tank at atmospheric pressure, below boiling.
References
- Q = m (h₂ − h₁)
- IAPWS-IF97 water at 1 atm
Questions and answers
What power heats 200 L from 25 °C to 60 °C in an hour?
About 8.5 kW at 95 % efficiency (8.1 kWh of heat).
How long with a 3 kW heater?
About 2 h 50 min.
Is 1.163 Wh per litre per kelvin right?
Yes, near room temperature; this calculator uses the exact enthalpy of water.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.