Worked example
Example: Peele's example: 500 ft shaft, 32 F outside, 55 F inside. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Depth (height of the air columns) | 152.40 m |
| Mean temperature of the intake column | 0 °C |
| Relative humidity of the intake air | 50.000 % |
| Mean temperature of the return column | 12.778 °C |
| Relative humidity of the return air | 95.000 % |
| Barometric pressure | 101.59 kPa |
| Mine resistance (N·s²/m⁸) | 0.050000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Intake air density | 1.2942 kg/m³ |
| Return air density | 1.2314 kg/m³ |
| Natural ventilating pressure (negative = reversed) | 93.994 Pa |
| Natural air flow through the mine (negative = reversed) | 43.358 m³/s |
Open this example in the calculator and change any input.
Formula
\(NVP = gH(\rho_i - \rho_r), \quad Q = \sqrt{\frac{NVP}{R}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(H\) | Depth (height of the air columns) | m |
| \(T_i\) | Mean temperature of the intake column | K |
| \(\phi_i\) | Relative humidity of the intake air | - |
| \(T_r\) | Mean temperature of the return column | K |
| \(\phi_r\) | Relative humidity of the return air | - |
| \(p_b\) | Barometric pressure | Pa |
| \(R\) | Mine resistance (N·s²/m⁸) | - |
| \(\rho_i\) | Intake air density | kg/m³ |
| \(\rho_r\) | Return air density | kg/m³ |
| \(NVP\) | Natural ventilating pressure (negative = reversed) | Pa |
| \(Q\) | Natural air flow through the mine (negative = reversed) | m³/s |
Method and standards
Difference of air-column weights.
Where it is used
- Mine ventilation planning and fan selection.
- Explaining seasonal airflow changes.
Common mistakes
- Ignoring humidity in warm return air.
- Treating natural pressure as constant through the year.
Assumptions and limits
- Equal column heights; mean column conditions.
References
- Peele (ed.)
- Mining Engineers' Handbook
- 3rd ed. (Wiley, 1941)
- sec. 14
- Mine Ventilation
- art. 12 (natural draft) and its worked example
- IAPWS-IF97 saturation pressure for the humid-air densities
Questions and answers
Why does natural ventilation change with the seasons?
Cold winter intake air is denser than warm mine air, driving air down the intake; in summer the difference shrinks or reverses.
How big is it?
Peele's example of a 500 ft shaft with 32 °F outside and 55 °F inside air gives about 2 lb/ft², roughly 94 Pa.
What do the defaults represent?
Peele's example: 500 ft columns, outside air 32 °F at 50 % and mine air 55 °F at 95 %, barometer 30 inHg, through a 0.05 N·s²/m⁸ mine.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.