FireCADCalc

Hazen–Williams Head Loss in Water Pipes

Friction head loss and pressure drop for water in a full pipe by the Hazen–Williams formula, from flow, diameter, length and the C factor.

Thermal power plantProcess steam and utilitiesFood, dairy and textilePump

Inputs

Examples: 50 L/s in 200 mm, 1000 m, C 12010 L/s in 100 mm, 500 m, C 140200 L/s in 400 mm, 2000 m, C 100

From your design standard for the pipe material and age; smooth plastic pipes are around 140–150, older steel and cast iron much lower.

Results

Hazen–Williams applies to water near room temperature in turbulent flow; use Darcy–Weisbach for other liquids or hot water.

Head loss18.595m
Pressure drop181.99kPa
Hydraulic gradient (m per 1000 m)9.2973
Velocity1.5915m/s

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 50 L/s in 200 mm, 1000 m, C 120. The inputs, in the units selected above:

InputValue
Water flow50.000 L/s
Pipe inside diameter200.00 mm
Pipe length1,000.0 m
Hazen–Williams C factor120.00 -
Water density (for the pressure drop)998.00 kg/m³

Applying the formula below gives:

ResultValue
Head loss14.891 m
Pressure drop145.74 kPa
Hydraulic gradient (m per 1000 m)14.891
Velocity1.5915 m/s

Open this example in the calculator and change any input.

Formula

\(v = \frac{Q}{\pi D^2/4} \qquad S = \left(\frac{v}{0.849\,C\,R^{0.63}}\right)^{1/0.54},\ R = \frac{D}{4} \qquad h_f = S\,L \qquad \Delta p = \rho g h_f\)

Variables

Symbol Meaning SI unit
\(Q\) flow m³/s
\(D\) inside diameter m
\(L\) length m
\(C\) Hazen–Williams factor –
\(\rho\) water density kg/m³
\(h_f\) head loss m
\(\Delta p\) pressure drop Pa
\(S\) hydraulic gradient, in m per 1000 m -
\(v\) velocity m/s
\(R\) hydraulic radius m
\(g\) standard gravity m/s²

Method and standards

Hazen–Williams velocity formula in SI units (k = 0.849), solved for the slope.

Where it is used

  • Raw water and fire water mains.
  • Cooling water pipelines.
  • Municipal supply.

Common mistakes

  • Using it for oil or hot water.
  • Using nominal diameter.
  • Not lowering C for old pipes.

Assumptions and limits

  • Water near room temperature; full pipe; turbulent flow.

References

  • Hazen–Williams formula (SI, k = 0.849)

Questions and answers

What is the loss for 50 L/s in a 200 mm pipe, 1 km, C 120?

14.9 m of head (146 kPa) at 1.59 m/s.

When is Hazen–Williams wrong?

Hot water, other liquids, very small or very large velocities: use Darcy–Weisbach.

What C should I use?

From your design standard for the material and age; C falls as pipes age.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.