Worked example
Example: 50 L/s in 200 mm, 1000 m, C 120. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Water flow | 50.000 L/s |
| Pipe inside diameter | 200.00 mm |
| Pipe length | 1,000.0 m |
| Hazen–Williams C factor | 120.00 - |
| Water density (for the pressure drop) | 998.00 kg/m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| Head loss | 14.891 m |
| Pressure drop | 145.74 kPa |
| Hydraulic gradient (m per 1000 m) | 14.891 |
| Velocity | 1.5915 m/s |
Open this example in the calculator and change any input.
Formula
\(v = \frac{Q}{\pi D^2/4} \qquad S = \left(\frac{v}{0.849\,C\,R^{0.63}}\right)^{1/0.54},\ R = \frac{D}{4} \qquad h_f = S\,L \qquad \Delta p = \rho g h_f\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q\) | flow | m³/s |
| \(D\) | inside diameter | m |
| \(L\) | length | m |
| \(C\) | Hazen–Williams factor | – |
| \(\rho\) | water density | kg/m³ |
| \(h_f\) | head loss | m |
| \(\Delta p\) | pressure drop | Pa |
| \(S\) | hydraulic gradient, in m per 1000 m | - |
| \(v\) | velocity | m/s |
| \(R\) | hydraulic radius | m |
| \(g\) | standard gravity | m/s² |
Method and standards
Hazen–Williams velocity formula in SI units (k = 0.849), solved for the slope.
Where it is used
- Raw water and fire water mains.
- Cooling water pipelines.
- Municipal supply.
Common mistakes
- Using it for oil or hot water.
- Using nominal diameter.
- Not lowering C for old pipes.
Assumptions and limits
- Water near room temperature; full pipe; turbulent flow.
References
- Hazen–Williams formula (SI, k = 0.849)
Questions and answers
What is the loss for 50 L/s in a 200 mm pipe, 1 km, C 120?
14.9 m of head (146 kPa) at 1.59 m/s.
When is Hazen–Williams wrong?
Hot water, other liquids, very small or very large velocities: use Darcy–Weisbach.
What C should I use?
From your design standard for the material and age; C falls as pipes age.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.