Worked example
Example: Cooling water, 2 passes, U-tubes, 6 m. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Tube-side mass flow | 216,000 kg/h |
| Tube inside diameter | 15.700 mm |
| Number of tubes | 400.00 - |
| Number of tube passes | 2.0000 - |
| Tube length | 6.0000 m |
| Density | 995.00 kg/m³ |
| Viscosity | 0.75000 mPa·s |
| Viscosity ratio bulk to wall | 1.1000 - |
| Tube type | U-tubes |
| Nozzle inside diameter | 200.00 mm |
| Shells in series | 1.0000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Tube-side Reynolds number | 32,439 |
| Tube velocity | 1.5574 m/s |
| Tube-side mass flux | 1,549.6 kg/(m²·s) |
| Darcy friction factor | 0.028221 |
| Friction loss in the tubes | 25.685 kPa |
| Velocity heads for entrance, exit and return losses | 1.7000 |
| Entrance, exit and return losses | 2.0514 kPa |
| Nozzle Reynolds number | 509,296 |
| Nozzle losses (all shells) | 2.7494 kPa |
| Total tube-side pressure drop | 30.485 kPa |
Open this example in the calculator and change any input.
Formula
\(\Delta P_f = \frac{fn_pLG^2}{2\rho D_i\phi}, \quad f = 0.4137Re^{-0.2585}\)
\(\Delta P_r = \alpha_r\frac{G^2}{2\rho}, \quad \alpha_r = 2n_p - 1.5 \;(\text{turbulent}), \quad \Delta P_n = 0.75N_s\frac{G_n^2}{\rho}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m\) | Tube-side mass flow | kg/s |
| \(D_i\) | Tube inside diameter | m |
| \(n_t\) | Number of tubes | - |
| \(n_p\) | Number of tube passes | - |
| \(L\) | Tube length | m |
| \(\rho\) | Density | kg/m³ |
| \(\mu\) | Viscosity | Pa·s |
| \(\mu/\mu_w\) | Viscosity ratio bulk to wall | - |
| \(\text{tubes}\) | Tube type | - |
| \(D_n\) | Nozzle inside diameter | m |
| \(N_s\) | Shells in series | - |
| \(Re\) | Tube-side Reynolds number | - |
| \(V\) | Tube velocity | m/s |
| \(G\) | Tube-side mass flux | kg/(m²·s) |
| \(f\) | Darcy friction factor | - |
| \(\Delta P_f\) | Friction loss in the tubes | Pa |
| \(\alpha_r\) | Velocity heads for entrance, exit and return losses | - |
| \(\Delta P_r\) | Entrance, exit and return losses | Pa |
| \(Re_n\) | Nozzle Reynolds number | - |
| \(\Delta P_n\) | Nozzle losses (all shells) | Pa |
| \(\Delta P_i\) | Total tube-side pressure drop | Pa |
Method and standards
Darcy friction in the tubes plus velocity-head allowances for headers and nozzles.
Where it is used
- Checking the tube-side pressure drop when choosing the number of passes.
- Rating existing exchangers.
Common mistakes
- Using the total mass flux instead of the flow per pass.
- Omitting the nozzle losses.
Assumptions and limits
- Single-phase flow; viscosity correction (μ/μ_w)^0.14 turbulent, ^0.25 laminar.
Questions and answers
Why not use four velocity heads per pass?
Kern's four per pass is conservative; the analysis of entrance, exit and return losses gives about 2n_p − 1.5 in turbulent flow, close to HEXTRAN's two per pass.
What friction factor is used?
The fit for heat-exchanger tubing, f = 0.4137 Re^−0.2585 (Darcy), slightly below commercial-pipe values; f = 64/Re in laminar flow.
What do the defaults represent?
An illustrative case: Cooling water, 2 passes, U-tubes, 6 m. Replace the inputs with your own data.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Serth, Process Heat Transfer: Principles and Applications (Academic Press, 2007), sec. 5.3.1, eqs. 5.1 to 5.5, Table 5.1, Appendix 5.A and Example 5.1