Worked example
Example: 40 °C, 30 %, 90 % effective, 40 MW. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Ambient dry bulb | 40.000 °C |
| Relative humidity | 30.000 % |
| Ambient pressure | 101.33 kPa |
| Cooler effectiveness (fogging ≈ 1) | 90.000 % |
| Compressor air flow (dry air) | 540,000 kg/h |
| Gas turbine output at ambient | 40.000 MW |
| Output gain per K of inlet cooling (%/K) | 0.60000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Wet bulb temperature | 25.093 °C |
| Compressor inlet temperature | 26.583 °C |
| Inlet cooling | 13.417 K |
| Output gain | 3.2200 MW |
| Water evaporated | 3.0571 t/h |
Open this example in the calculator and change any input.
Formula
\(T_2 = T_{db} - \varepsilon(T_{db} - T_{wb}), \quad \Delta P = \frac{s}{100}P_0(T_{db} - T_2), \quad \dot m_w = \dot m_a(W_2 - W_1)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(T_{db}\) | Ambient dry bulb | K |
| \(\phi\) | Relative humidity | - |
| \(p\) | Ambient pressure | Pa |
| \(\varepsilon\) | Cooler effectiveness (fogging ≈ 1) | - |
| \(\dot m_a\) | Compressor air flow | kg/s |
| \(P_0\) | Gas turbine output at ambient | W |
| \(s\) | Output gain per K of inlet cooling (%/K) | - |
| \(T_{wb}\) | Wet bulb temperature | K |
| \(T_2\) | Compressor inlet temperature | K |
| \(\Delta T\) | Inlet cooling | K |
| \(\Delta P\) | Output gain | W |
| \(\dot m_w\) | Water evaporated | kg/s |
Method and standards
Psychrometrics with the maker's sensitivity.
Where it is used
- Peak-season output enhancement.
- Water budget for coolers and foggers.
Common mistakes
- Using dry-bulb sensitivity for a different gas turbine.
- Forgetting water quality for foggers.
Assumptions and limits
- Adiabatic cooling along the wet-bulb line; s is entered in %/K, hence the division by 100.
- The air flow is taken as dry air in the water balance; using the moist-air flow instead changes the water by 1–3 % in hot humid weather.
- Air whose wet bulb is below 0 °C is rejected: the method assumes liquid water.
References
- Psychrometric wet-bulb relation (ASHRAE Handbook — Fundamentals, ch. 1) with IAPWS-IF97 saturation; output from the maker's correction factor
Questions and answers
Why does cooling the inlet raise output?
Colder air is denser, so the compressor passes more mass; output falls roughly 0.5–0.8 % per K of ambient rise.
When does it work best?
In hot, dry weather, when the wet-bulb depression is large.
What do the defaults give?
40 °C at 30 % RH (wet bulb about 25 °C), 90 % effectiveness: about 13 K of cooling, roughly 3.2 MW more on a 40 MW unit, using about 3 t/h of water.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.