Worked example
Example: 15 MW condensing, 60 t/h at 66 bar(a) / 485 °C, feed 150 °C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Main steam flow | 60,000 kg/h |
| Inlet steam pressure (absolute) | 66.000 bar |
| Inlet steam condition | Superheated at the temperature below |
| Inlet steam temperature (superheated only) | 485.00 °C |
| Final feedwater temperature (boiler inlet) | 150.00 °C |
| Generator output | 15.000 MW |
Applying the formula below gives:
| Result | Value |
|---|---|
| Turbine heat rate | 10,975 kJ/kWh |
| Turbine cycle efficiency | 32.803 % |
| Heat added to the steam | 45.728 MW |
Open this example in the calculator and change any input.
Formula
\(\dot Q = \dot m_s\,(h_1 - h_{fw}) \qquad HR = \frac{\dot Q}{P_{el}} \qquad \eta_c = \frac{P_{el}}{\dot Q} = \frac{1}{HR}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m_s\) | main steam flow | kg/s |
| \(p_1\) | main steam pressure, absolute | Pa |
| \(\text{state}\) | dry saturated or superheated steam | – |
| \(T_1\) | main steam temperature | K |
| \(T_{fw}\) | final feedwater temperature | K |
| \(P_{el}\) | generator output | W |
| \(HR\) | turbine heat rate | J/J |
| \(\eta_c\) | turbine cycle efficiency | – |
| \(\dot Q\) | heat added to the steam | W |
| \(h_1\) | main steam enthalpy | J/kg |
| \(h_{fw}\) | feedwater enthalpy | J/kg |
Method and standards
Turbine heat rate as heat added to the working fluid per unit of generator output, the definition used in ASME PTC 6 for non-reheat units, with enthalpies from FireCAD's IAPWS-IF97. Shown in kJ/kWh; 3600 kJ/kWh is 100 % efficiency.
Where it is used
- Acceptance and periodic tests of turbo-generators.
- Comparing turbine offers and checking design heat balances.
- Converting to plant heat rate and fuel consumption.
Common mistakes
- Using the boiler outlet feedwater temperature before the last heater.
- Mixing gross (generator) and net (after auxiliaries) output.
- Leaving out reheat heat for reheat units.
Assumptions and limits
- Non-reheat cycle; feedwater enthalpy at main steam pressure (the real feed pressure is higher; small effect); output measured at the generator terminals.
- For back-pressure (cogeneration) sets all the heat is charged to power, with no credit for the process steam: the heat rate is then very high and not a measure of the turbine's quality.
- Output above the heat added is rejected.
References
- IAPWS R7-97(2012) IF97
- ASME PTC 6 (turbine heat rate definition)
Questions and answers
How is turbine heat rate calculated?
Heat added to the steam per kWh generated. 60 t/h at 66 bar(a) and 485 °C from feedwater at 150 °C takes 45.7 MW of heat; at 15 MW output the heat rate is 10 975 kJ/kWh (2621 kcal/kWh), a cycle efficiency of 32.8 %.
What is the difference from plant heat rate?
Plant heat rate divides the fuel heat by the output, so it includes the boiler efficiency. Turbine heat rate ÷ boiler efficiency ≈ plant heat rate.
My turbine has reheat. Can I use this?
Not directly: add the reheat heat, m_rh (h_hot RH − h_cold RH), to the heat added. This calculator covers non-reheat sets.
Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.