Worked example
Example: 1100 °C gas, 300 °C tubes. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Gas temperature | 1,100.0 °C |
| Wall (tube surface) temperature | 300.00 °C |
| Gas emissivity at T_g | 25.000 % |
| Gas absorptivity for wall radiation | 30.000 % |
| Wall emissivity | 80.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Net radiant heat flux to the wall | 43.707 kW/m² |
| Radiation coefficient q/(T_g − T_w) | 54.634 W/(m²·K) |
Open this example in the calculator and change any input.
Formula
\(q = \sigma\frac{\varepsilon_w + 1}{2}\left(\varepsilon_g T_g^4 - \alpha_g T_w^4\right), \quad h_r = \frac{q}{T_g - T_w}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(T_g\) | Gas temperature | K |
| \(T_w\) | Wall (tube surface) temperature | K |
| \(\varepsilon_g\) | Gas emissivity at T_g | - |
| \(\alpha_g\) | Gas absorptivity for wall radiation | - |
| \(\varepsilon_w\) | Wall emissivity | - |
| \(q\) | Net radiant heat flux to the wall | W/m² |
| \(h_r\) | Radiation coefficient q/(T_g − T_w) | W/(m²·K) |
Method and standards
Hottel's gray-wall approximation: the net flux from a gray gas to a gray enclosure wall, with the effective wall emissivity \((\varepsilon_w + 1)/2\) for walls of emissivity above about 0.7.
Where it is used
- Superheater and convection bank radiation.
- Furnace design checks.
Common mistakes
- Celsius in the fourth power.
Assumptions and limits
- Gray walls, uniform gas. The flux is per unit of the wall (enclosure) surface the gas sees; for tube banks use it with the area the coefficient is referred to.
- The gas emissivity must be above zero and the net flux positive; inconsistent emissivity and absorptivity are rejected.
References
- q = σ (ε_w + 1)/2 (ε_g T_g⁴ − α_g T_w⁴) (Hottel and Sarofim, Radiative Transfer, McGraw-Hill, 1967; McAdams, Heat Transmission, 3rd ed., 1954; Perry's Chemical Engineers' Handbook)
- Stefan–Boltzmann constant 5.670374419 × 10⁻⁸ W/m²K⁴ (CODATA 2018)
Questions and answers
Why is absorptivity different from emissivity?
The gas absorbs radiation from the cooler wall with a different spectrum than it emits at its own temperature.
Why (ε_w + 1)/2?
Radiation not absorbed on first strike is reflected and partly absorbed elsewhere in the enclosure.
Luminous flames?
Soot and ash raise ε_g well above the clean-gas value.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.