Worked example
Example: Illustrative 10 Nm3/min at 8 bar(a). The inputs, in the units selected above:
| Input | Value |
|---|---|
| Dried air flow | 600.00 Nm³/h |
| Dryer operating pressure (absolute) | 8.0000 bar |
| Purge (regeneration) pressure (absolute) | 1.0300 bar |
| Purge-to-feed actual volume ratio (Skarstrom ≥ 1) | 1.1500 - |
| Compressor specific energy | 0.11000 kWh/m³ |
| Running hours per year | 8,000.0 h |
| Electricity price per kWh | 8.0000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Purge as share of dried air | 14.806 % |
| Purge flow | 88.837 Nm³/h |
| Compressor power for purge | 9.7721 kW |
| Annual energy | 78.177 MWh |
| Annual cost | 625,416 |
Open this example in the calculator and change any input.
Formula
\(\phi = r_S\frac{p_{purge}}{p_{line}}, \quad Q_p = \phi Q, \quad P_p = Q_pe\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q\) | Dried air flow | Nm³/s |
| \(p_{line}\) | Dryer operating pressure (absolute) | Pa |
| \(p_{purge}\) | Purge (regeneration) pressure (absolute) | Pa |
| \(r_S\) | Purge-to-feed actual volume ratio (Skarstrom ≥ 1) | - |
| \(e\) | Compressor specific energy | J/m³ |
| \(t\) | Running hours per year | s |
| \(c_e\) | Electricity price per kWh | - |
| \(\phi\) | Purge as share of dried air | - |
| \(Q_p\) | Purge flow | Nm³/s |
| \(P_p\) | Compressor power for purge | W |
| \(E\) | Annual energy | J |
| \(C\) | Annual cost | - |
Method and standards
Purge loss.
Where it is used
- Compressed air audits.
- Choosing dryer type.
Common mistakes
- Using gauge pressures in the ratio.
- Forgetting dryers run purge at full flow even at low demand.
Assumptions and limits
- Fixed-cycle heatless dryer; purge at the stated pressure.
References
- Skarstrom purge criterion for pressure-swing adsorption
Questions and answers
Why does a heatless dryer use so much air?
It regenerates the desiccant by expanding dry product air to atmosphere; at 8 bar(a) each Nm³ of purge expands about eight times.
How can purge be reduced?
Dew-point demand switching, heated or blower-purge regeneration, or a refrigerated dryer where −40 °C dew point is not needed.
What do the defaults represent?
An illustrative 10 Nm³/min heatless dryer at 8 bar(a) purging to 1.03 bar(a), ratio 1.15, 0.11 kWh/Nm³, 8,000 h at 8 per kWh.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Skarstrom, Heatless Fractionation of Gases over Solid Adsorbents, in Recent Developments in Separation Science (CRC, 1972), Ruthven, Farooq and Knaebel, Pressure Swing Adsorption (VCH, 1994)