Compressor Intercooler Duty, Condensate and Cooling Water

Heat removed in an air compressor intercooler or aftercooler, the condensate formed from the humid air at the cooler pressure and the cooling water flow.

Thermal power plantProcess steam and utilities

Inputs

Examples: Illustrative aftercooler 1 kg/s, 150 to 35 C at 7 barAftercooler 8 bar, 120 to 35 CDry air, no condensate

Accepted: 3.6 to 360,000 kg/h
Accepted: 0 to 0.05 kg/kg
Accepted: 100 to 5,000 kPa
Accepted: 6.85 to 276.85 °C
Accepted: 1.85 to 126.85 °C
Accepted: 0.9 to 1.1 kJ/(kg·K)
Accepted: 1 to 40 K

Results

Humid air as an ideal mixture: W_sat = (M_w/M_a)p_s/(p − p_s) at the outlet temperature (IAPWS-IF97 saturation); water above that condenses, releasing latent heat. Vapour c_p 1,870 J/(kg·K) and cooling water c_p 4,186 J/(kg·K).

Saturation humidity ratio at outlet0.005041kg/kg
Condensate formed25.051kg/h
Sensible heat removed118.16kW
Latent heat from condensation16.825kW
Total cooler duty134.98kW
Cooling water flow11,608kg/h

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative aftercooler 1 kg/s, 150 to 35 C at 7 bar. The inputs, in the units selected above:

InputValue
Dry air mass flow3,600.0 kg/h
Inlet humidity ratio0.012000 kg/kg
Cooler pressure (absolute)700.00 kPa
Air temperature entering the cooler150.00 °C
Air temperature leaving the cooler35.000 °C
Dry air specific heat1.0050 kJ/(kg·K)
Cooling water temperature rise10.000 K

Applying the formula below gives:

ResultValue
Saturation humidity ratio at outlet0.005041 kg/kg
Condensate formed25.051 kg/h
Sensible heat removed118.16 kW
Latent heat from condensation16.825 kW
Total cooler duty134.98 kW
Cooling water flow11,608 kg/h

Open this example in the calculator and change any input.

Formula

\(W_{sat} = \frac{M_w}{M_a}\frac{p_s(T_{out})}{p - p_s}, \quad \dot m_c = \dot m_{da}(W_1 - W_{sat}), \quad \dot Q = \dot Q_s + \dot m_ch_{fg}\)

Variables

Symbol Meaning SI unit
\(\dot m_{da}\) Dry air mass flow kg/s
\(W_1\) Inlet humidity ratio kg/kg
\(p\) Cooler pressure (absolute) Pa
\(T_{in}\) Air temperature entering the cooler K
\(T_{out}\) Air temperature leaving the cooler K
\(c_p\) Dry air specific heat J/(kg·K)
\(\Delta T_w\) Cooling water temperature rise K
\(W_{sat}\) Saturation humidity ratio at outlet kg/kg
\(\dot m_c\) Condensate formed kg/s
\(\dot Q_s\) Sensible heat removed W
\(\dot Q_l\) Latent heat from condensation W
\(\dot Q\) Total cooler duty W
\(\dot m_w\) Cooling water flow kg/s

Method and standards

Cooler energy balance.

Where it is used

  • Compressor package and cooling water design.
  • Condensate drain sizing.

Common mistakes

  • Ignoring latent heat.
  • Using atmospheric pressure for the saturation humidity ratio.

Assumptions and limits

  • Ideal humid air; condensate leaves at the outlet temperature.

References

  • Humid-air energy balance of a compressor cooler

Questions and answers

Why does an intercooler produce water?

Compression raises the vapour partial pressure; cooling the compressed air back to near ambient pushes it past saturation, so water drops out.

How much of the duty is latent?

Often 10–25 % in humid climates, so ignoring condensation undersizes the cooler and the drain.

What do the defaults represent?

An illustrative aftercooler: 1 kg/s of air with humidity 0.012 kg/kg cooled from 150 °C to 35 °C at 7 bar absolute, with a 10 K cooling water rise.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Brown, Compressors: Selection and Sizing, 3rd ed. (Gulf Professional, 2005)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.