Worked example
Example: Illustrative aftercooler 1 kg/s, 150 to 35 C at 7 bar. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Dry air mass flow | 3,600.0 kg/h |
| Inlet humidity ratio | 0.012000 kg/kg |
| Cooler pressure (absolute) | 700.00 kPa |
| Air temperature entering the cooler | 150.00 °C |
| Air temperature leaving the cooler | 35.000 °C |
| Dry air specific heat | 1.0050 kJ/(kg·K) |
| Cooling water temperature rise | 10.000 K |
Applying the formula below gives:
| Result | Value |
|---|---|
| Saturation humidity ratio at outlet | 0.005041 kg/kg |
| Condensate formed | 25.051 kg/h |
| Sensible heat removed | 118.16 kW |
| Latent heat from condensation | 16.825 kW |
| Total cooler duty | 134.98 kW |
| Cooling water flow | 11,608 kg/h |
Open this example in the calculator and change any input.
Formula
\(W_{sat} = \frac{M_w}{M_a}\frac{p_s(T_{out})}{p - p_s}, \quad \dot m_c = \dot m_{da}(W_1 - W_{sat}), \quad \dot Q = \dot Q_s + \dot m_ch_{fg}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot m_{da}\) | Dry air mass flow | kg/s |
| \(W_1\) | Inlet humidity ratio | kg/kg |
| \(p\) | Cooler pressure (absolute) | Pa |
| \(T_{in}\) | Air temperature entering the cooler | K |
| \(T_{out}\) | Air temperature leaving the cooler | K |
| \(c_p\) | Dry air specific heat | J/(kg·K) |
| \(\Delta T_w\) | Cooling water temperature rise | K |
| \(W_{sat}\) | Saturation humidity ratio at outlet | kg/kg |
| \(\dot m_c\) | Condensate formed | kg/s |
| \(\dot Q_s\) | Sensible heat removed | W |
| \(\dot Q_l\) | Latent heat from condensation | W |
| \(\dot Q\) | Total cooler duty | W |
| \(\dot m_w\) | Cooling water flow | kg/s |
Method and standards
Cooler energy balance.
Where it is used
- Compressor package and cooling water design.
- Condensate drain sizing.
Common mistakes
- Ignoring latent heat.
- Using atmospheric pressure for the saturation humidity ratio.
Assumptions and limits
- Ideal humid air; condensate leaves at the outlet temperature.
References
- Humid-air energy balance of a compressor cooler
Questions and answers
Why does an intercooler produce water?
Compression raises the vapour partial pressure; cooling the compressed air back to near ambient pushes it past saturation, so water drops out.
How much of the duty is latent?
Often 10–25 % in humid climates, so ignoring condensation undersizes the cooler and the drain.
What do the defaults represent?
An illustrative aftercooler: 1 kg/s of air with humidity 0.012 kg/kg cooled from 150 °C to 35 °C at 7 bar absolute, with a 10 K cooling water rise.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Brown, Compressors: Selection and Sizing, 3rd ed. (Gulf Professional, 2005)