Low Loss Header (Hydraulic Separator) Sizing

Diameter of a low loss header for the larger of the primary and secondary flows, and the mixed flow temperatures it delivers to each side.

Inputs

Examples: Illustrative boiler house, secondary flow largerPrimary flow largerChilled water, small plant

Accepted: 0.0036 to 36,000 m³/h
Accepted: 0.0036 to 36,000 m³/h
0.1 to 0.2 m/s lets air and dirt separate and keeps the two circuits independent.Accepted: 0.02 to 1 m/s
Accepted: 5 to 1,000 mm
Accepted: 0 to 150 °C
Accepted: 0 to 150 °C

Results

The header joins the primary and secondary circuits through a short, wide vessel so that neither pump drives the other. Sized for the larger flow at about 0.1–0.2 m/s (and at least three times the largest connecting pipe), its pressure drop is negligible. When the secondary flow is larger, return water mixes into the supply and the system receives a lower temperature; when the primary flow is larger, supply water short-circuits and the boiler or chiller sees a higher (or lower) return. Mixed temperatures assume equal density and specific heat on both sides.

Header diameter for the velocity limit325.74mm
Header diameter by the three-diameter rule210.90mm
Header diameter to use (larger of the two)325.74mm
Velocity in the header at that diameter0.10000m/s
Secondary flow temperature after mixing70.000°C
Primary return temperature after mixing51.667°C
Flow through the header (difference of the flows)8.0000m³/h

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative boiler house, secondary flow larger. The inputs, in the units selected above:

InputValue
Primary (boiler or chiller) flow20.000 m³/h
Secondary (system) flow24.000 m³/h
Highest velocity in the header0.15000 m/s
Inside diameter of the largest connecting pipe62.700 mm
Primary flow temperature80.000 °C
Secondary return temperature60.000 °C

Applying the formula below gives:

ResultValue
Header diameter for the velocity limit237.88 mm
Header diameter by the three-diameter rule188.10 mm
Header diameter to use (larger of the two)237.88 mm
Velocity in the header at that diameter0.15000 m/s
Secondary flow temperature after mixing76.667 °C
Primary return temperature after mixing60.000 °C
Flow through the header (difference of the flows)4.0000 m³/h

Open this example in the calculator and change any input.

Formula

\(d = \max\left(\sqrt{\frac{4\dot V_{max}}{\pi v_{max}}},\ 3d_c\right), \quad T_{ss} = \frac{\dot V_p T_{ps} + (\dot V_s - \dot V_p)T_{sr}}{\dot V_s}\)

Variables

Symbol Meaning SI unit
\(\dot V_p\) Primary (boiler or chiller) flow m³/s
\(\dot V_s\) Secondary (system) flow m³/s
\(v_{max}\) Highest velocity in the header m/s
\(d_c\) Inside diameter of the largest connecting pipe m
\(T_{ps}\) Primary flow temperature K
\(T_{sr}\) Secondary return temperature K
\(d_v\) Header diameter for the velocity limit m
\(3d_c\) Header diameter by the three-diameter rule m
\(d\) Header diameter to use (larger of the two) m
\(v\) Velocity in the header at that diameter m/s
\(T_{ss}\) Secondary flow temperature after mixing K
\(T_{pr}\) Primary return temperature after mixing K
\(\dot V_m\) Flow through the header (difference of the flows) m³/s

Method and standards

Low loss header.

Where it is used

  • Boiler houses with several boilers and heating circuits.
  • Chilled-water plants with primary and secondary pumps.

Common mistakes

  • Sizing the header for the primary flow only.
  • Expecting design flow temperature in the system when the secondary flow exceeds the primary.

Assumptions and limits

  • Equal density and specific heat; full mixing in the header.

References

  • Continuity at the header and mixing energy balance (hydraulic separator practice)

Questions and answers

How do I size a low loss header?

Take the larger of the primary and secondary flows and choose a diameter that keeps the velocity at 0.1–0.2 m/s, and at least three times the largest connecting pipe.

Why is my boiler return too hot?

The primary flow is larger than the secondary flow, so hot supply water short-circuits through the header into the boiler return.

What do the defaults represent?

An illustrative 20 m³/h boiler circuit and 24 m³/h heating system with 80 °C flow and 60 °C return, DN 65 connections.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.