Worked example
Example: Illustrative boiler house, secondary flow larger. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Primary (boiler or chiller) flow | 20.000 m³/h |
| Secondary (system) flow | 24.000 m³/h |
| Highest velocity in the header | 0.15000 m/s |
| Inside diameter of the largest connecting pipe | 62.700 mm |
| Primary flow temperature | 80.000 °C |
| Secondary return temperature | 60.000 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Header diameter for the velocity limit | 237.88 mm |
| Header diameter by the three-diameter rule | 188.10 mm |
| Header diameter to use (larger of the two) | 237.88 mm |
| Velocity in the header at that diameter | 0.15000 m/s |
| Secondary flow temperature after mixing | 76.667 °C |
| Primary return temperature after mixing | 60.000 °C |
| Flow through the header (difference of the flows) | 4.0000 m³/h |
Open this example in the calculator and change any input.
Formula
\(d = \max\left(\sqrt{\frac{4\dot V_{max}}{\pi v_{max}}},\ 3d_c\right), \quad T_{ss} = \frac{\dot V_p T_{ps} + (\dot V_s - \dot V_p)T_{sr}}{\dot V_s}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot V_p\) | Primary (boiler or chiller) flow | m³/s |
| \(\dot V_s\) | Secondary (system) flow | m³/s |
| \(v_{max}\) | Highest velocity in the header | m/s |
| \(d_c\) | Inside diameter of the largest connecting pipe | m |
| \(T_{ps}\) | Primary flow temperature | K |
| \(T_{sr}\) | Secondary return temperature | K |
| \(d_v\) | Header diameter for the velocity limit | m |
| \(3d_c\) | Header diameter by the three-diameter rule | m |
| \(d\) | Header diameter to use (larger of the two) | m |
| \(v\) | Velocity in the header at that diameter | m/s |
| \(T_{ss}\) | Secondary flow temperature after mixing | K |
| \(T_{pr}\) | Primary return temperature after mixing | K |
| \(\dot V_m\) | Flow through the header (difference of the flows) | m³/s |
Method and standards
Low loss header.
Where it is used
- Boiler houses with several boilers and heating circuits.
- Chilled-water plants with primary and secondary pumps.
Common mistakes
- Sizing the header for the primary flow only.
- Expecting design flow temperature in the system when the secondary flow exceeds the primary.
Assumptions and limits
- Equal density and specific heat; full mixing in the header.
References
- Continuity at the header and mixing energy balance (hydraulic separator practice)
Questions and answers
How do I size a low loss header?
Take the larger of the primary and secondary flows and choose a diameter that keeps the velocity at 0.1–0.2 m/s, and at least three times the largest connecting pipe.
Why is my boiler return too hot?
The primary flow is larger than the secondary flow, so hot supply water short-circuits through the header into the boiler return.
What do the defaults represent?
An illustrative 20 m³/h boiler circuit and 24 m³/h heating system with 80 °C flow and 60 °C return, DN 65 connections.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.