Worked example
Example: Illustrative 2.4 m beam, 14 C water. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Beam active length | 2.4000 m |
| Coil specific capacity per kelvin per metre | 45.000 - |
| Room temperature | 24.000 °C |
| Room relative humidity | 50.000 % |
| Water supply temperature | 14.000 °C |
| Water temperature rise | 2.5000 K |
| Primary air flow | 25.000 L/s |
| Primary air supply temperature | 14.000 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Coil sensible capacity | 945.00 W |
| Primary air sensible capacity | 301.80 W |
| Total sensible capacity | 1,246.8 W |
| Chilled water flow | 0.090301 L/s |
| Water supply margin above room dew point | 1.0536 K |
Open this example in the calculator and change any input.
Formula
\(\dot Q_{coil} = q'L(T_r - \bar T_w), \quad \dot Q_{pa} = \rho c_p\dot V_{pa}(T_r - T_{pa}), \quad \dot V_w = \frac{\dot Q_{coil}}{\rho_wc_w\Delta T_w}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(L\) | Beam active length | m |
| \(q'\) | Coil specific capacity per kelvin per metre | - |
| \(T_r\) | Room temperature | K |
| \(\varphi_r\) | Room relative humidity | - |
| \(T_{w,in}\) | Water supply temperature | K |
| \(\Delta T_w\) | Water temperature rise | K |
| \(\dot V_{pa}\) | Primary air flow | m³/s |
| \(T_{pa}\) | Primary air supply temperature | K |
| \(\dot Q_{coil}\) | Coil sensible capacity | W |
| \(\dot Q_{pa}\) | Primary air sensible capacity | W |
| \(\dot Q\) | Total sensible capacity | W |
| \(\dot V_w\) | Chilled water flow | m³/s |
| \(T_{w,in} - T_d\) | Water supply margin above room dew point | K |
Method and standards
Chilled beam.
Where it is used
- Office and laboratory cooling design.
- Checking beam capacity against loads.
Common mistakes
- Supplying water below the dew point.
- Counting latent load on the beam.
Assumptions and limits
- Maker's specific capacity at the operating nozzle pressure; sensible only.
References
- Active chilled beam sensible balance
Questions and answers
Why must chilled beam water stay warm?
Beams have no condensate drain; water below the room dew point would wet the coil and drip.
Who handles the latent load?
The dehumidified primary air from the air-handling unit.
What do the defaults represent?
An illustrative 2.4 m beam of 45 W/(m·K) with 14 °C water rising 2.5 K, 25 L/s of 14 °C primary air, room at 24 °C and 50 % RH.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Howell, Sauer and Coad, Principles of Heating, Ventilating and Air Conditioning, 8th ed. (ASHRAE, 2017)