Active Chilled Beam: Coil, Primary Air and Water Flow

Sensible cooling of an active chilled beam from its coil's specific capacity and from primary air, the chilled water flow and the dew-point margin.

Process steam and utilitiesFood, dairy and textile

Inputs

Examples: Illustrative 2.4 m beam, 14 C waterHigh-capacity 3 m beam, 15 C waterHumid room, small margin

Accepted: 0.5 to 10 m
Accepted: 5 to 200
Accepted: 17 to 30 °C
Accepted: 20 to 80 %
Accepted: 10 to 20 °C
Accepted: 0.5 to 6 K
Accepted: 1 to 500 L/s
Accepted: 10 to 20 °C

Results

Coil capacity = q′·L·(T_room − T_w,mean), q′ from the maker for the beam's primary air nozzle pressure; primary air adds ρc_pV̇(T_r − T_pa) (ρ = 1.2 kg/m³). Chilled beams are sensible-only: keep supply water at least about 1 K above the room dew point and handle latent load with dry primary air.

Coil sensible capacity504.00W
Primary air sensible capacity217.30W
Total sensible capacity721.30W
Chilled water flow0.060201L/s
Water supply margin above room dew point0.23715K

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 2.4 m beam, 14 C water. The inputs, in the units selected above:

InputValue
Beam active length2.4000 m
Coil specific capacity per kelvin per metre45.000 -
Room temperature24.000 °C
Room relative humidity50.000 %
Water supply temperature14.000 °C
Water temperature rise2.5000 K
Primary air flow25.000 L/s
Primary air supply temperature14.000 °C

Applying the formula below gives:

ResultValue
Coil sensible capacity945.00 W
Primary air sensible capacity301.80 W
Total sensible capacity1,246.8 W
Chilled water flow0.090301 L/s
Water supply margin above room dew point1.0536 K

Open this example in the calculator and change any input.

Formula

\(\dot Q_{coil} = q'L(T_r - \bar T_w), \quad \dot Q_{pa} = \rho c_p\dot V_{pa}(T_r - T_{pa}), \quad \dot V_w = \frac{\dot Q_{coil}}{\rho_wc_w\Delta T_w}\)

Variables

Symbol Meaning SI unit
\(L\) Beam active length m
\(q'\) Coil specific capacity per kelvin per metre -
\(T_r\) Room temperature K
\(\varphi_r\) Room relative humidity -
\(T_{w,in}\) Water supply temperature K
\(\Delta T_w\) Water temperature rise K
\(\dot V_{pa}\) Primary air flow m³/s
\(T_{pa}\) Primary air supply temperature K
\(\dot Q_{coil}\) Coil sensible capacity W
\(\dot Q_{pa}\) Primary air sensible capacity W
\(\dot Q\) Total sensible capacity W
\(\dot V_w\) Chilled water flow m³/s
\(T_{w,in} - T_d\) Water supply margin above room dew point K

Method and standards

Chilled beam.

Where it is used

  • Office and laboratory cooling design.
  • Checking beam capacity against loads.

Common mistakes

  • Supplying water below the dew point.
  • Counting latent load on the beam.

Assumptions and limits

  • Maker's specific capacity at the operating nozzle pressure; sensible only.

References

  • Active chilled beam sensible balance

Questions and answers

Why must chilled beam water stay warm?

Beams have no condensate drain; water below the room dew point would wet the coil and drip.

Who handles the latent load?

The dehumidified primary air from the air-handling unit.

What do the defaults represent?

An illustrative 2.4 m beam of 45 W/(m·K) with 14 °C water rising 2.5 K, 25 L/s of 14 °C primary air, room at 24 °C and 50 % RH.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Howell, Sauer and Coad, Principles of Heating, Ventilating and Air Conditioning, 8th ed. (ASHRAE, 2017)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.