Worked example
Example: Month: 600 000 kWh, 1200 kVA demand, pf 0.95, 720 h, 7/kWh, 400/kVA. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Energy used in the period | 600,000 kWh |
| Maximum demand | 1,200.0 kVA |
| Average power factor | 95.000 % |
| Hours in the billing period | 720.00 h |
| Energy rate per kWh (your currency) | 7.0000 - |
| Demand rate per kVA per period (your currency) | 400.00 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Total cost (your currency) | 4,680,000 |
| Energy charge | 4,200,000 |
| Demand charge | 480,000 |
| Average cost per kWh | 7.8000 |
| Load factor | 73.099 % |
Open this example in the calculator and change any input.
Formula
\(C_e = E\,c_e \qquad C_d = S_{md}\,c_d \qquad C = C_e + C_d \qquad \bar c = \frac{C}{E} \qquad LF = \frac{E}{S_{md}\cos\varphi\,t}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(E\) | energy used | J |
| \(S_{md}\) | maximum demand | VA |
| \(\cos\varphi\) | average power factor | – |
| \(t\) | hours in the period | s |
| \(c_e\) | energy rate per kWh | – |
| \(c_d\) | demand rate per kVA | – |
| \(C\) | total cost | – |
| \(C_e\) | energy charge | – |
| \(C_d\) | demand charge | – |
| \(\bar c\) | average cost per kWh | – |
| \(LF\) | load factor | – |
Method and standards
Two-part tariff: energy and maximum demand charges; load factor relative to maximum demand converted to kW.
Where it is used
- Checking utility bills.
- Valuing power factor correction and load management.
- Budgeting plant power.
Common mistakes
- Using kW demand where the tariff charges kVA.
- Ignoring contracted minimum demand.
- Comparing average cost across tariffs.
Assumptions and limits
- Single-rate energy and demand charges.
- The load factor converts the maximum demand to kW with the average power factor; the power factor at the time of the peak may differ.
References
- Two-part tariff arithmetic
Questions and answers
How is an industrial electricity bill made up?
Energy charge plus demand charge. 600 000 kWh at 7 and 1200 kVA demand at 400 cost 4.68 million, an average of 7.80 per kWh; the load factor is 73 %.
How do I lower the average cost?
Flatten the load (higher load factor), improve power factor to cut kVA demand, and shift loads off peak where the tariff rewards it.
What is not included?
Taxes, power-factor penalties or rebates and time-of-day rates.
Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.