Worked example
Example: 90° V-notch, 200 mm head, Cd 0.59. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Weir type | V-notch (triangular) |
| Crest width (rectangular) | 1.0000 m |
| Notch angle (V-notch) | 90.000 ° |
| Head over the crest or notch bottom | 200.00 mm |
| Discharge coefficient | 0.59000 - |
| Target flow for the head output (0 = none) | 0 m³/h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Flow over the weir | 24.929 L/s |
Open this example in the calculator and change any input.
Formula
\(Q = \frac{2}{3} C_d\, b \sqrt{2g}\, H^{3/2} \ \text{(rectangular)}\)
\(Q = \frac{8}{15} C_d \tan\frac{\theta}{2} \sqrt{2g}\, H^{5/2} \ \text{(V-notch)}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\text{type}\) | weir type | - |
| \(b\) | crest width | m |
| \(\theta\) | notch angle | rad |
| \(H\) | head over the crest | m |
| \(C_d\) | discharge coefficient | - |
| \(Q_t\) | target flow | m³/s |
| \(Q\) | flow over the weir | m³/s |
| \(H_t\) | head for the target flow | m |
| \(g\) | standard gravity | m/s² |
Method and standards
Integrating the ideal velocity √(2gh) over the opening gives the weir equations; the discharge coefficient accounts for contraction and losses. The head for a target flow inverts the same equation.
Where it is used
- Measuring effluent and cooling tower blowdown flows.
- Sizing weirs in tanks and channels.
- Checking clarifier and settling tank outlets.
Common mistakes
- Measuring head too close to the weir (the surface draws down).
- Letting the nappe cling to the weir (it must be aerated).
- Using the coefficient for a different notch angle.
Assumptions and limits
One constant discharge coefficient is used at every head. Standard weir methods (Kindsvater–Carter, ISO 1438) make the coefficient depend on head, crest height and width ratio, add an approach-velocity correction and set limits on head and dimensions; none of these is applied, so for metering use a calibrated coefficient or the standard's method.
Free, aerated nappe; approach velocity negligible.
References
- Sharp-crested weir equations
Questions and answers
What flow does a 90° V-notch pass at 200 mm head?
About 24.9 L/s with Cd 0.59.
Why use a V-notch for small flows?
Flow rises with head to the power 2.5, so small flows still give a readable head.
What coefficient should I use?
About 0.6 for sharp-crested weirs; for accurate metering use the coefficient for your weir's geometry from the weir standard or a calibration.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.