FireCADCalc

Water Demand from Population and Per Capita Supply

Present and future population by geometric growth, average daily water demand, maximum day and peak hour flows from per capita supply and peak factors.

Inputs

Examples: Colony of 5000, 30 yearsTown of 50 000, 20 years

Per person per day, from your water supply standard for the type of town or colony; choose litres or US gallons.

Results

Design population P₀(1 + r)ⁿ67,343
Average daily demand10,101m³/d
Maximum day demand15,152m³/d
Peak hour flow263.06L/s

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Colony of 5000, 30 years. The inputs, in the units selected above:

InputValue
Present population5,000.0 -
Annual growth rate2.0000 %
Design period (years)30.000 -
Per capita supply (volume per person per day)135.00 L
Maximum day factor1.8000 -
Peak hour factor2.7000 -

Applying the formula below gives:

ResultValue
Design population P₀(1 + r)ⁿ9,056.8
Average daily demand1,222.7 m³/d
Maximum day demand2,200.8 m³/d
Peak hour flow38.208 L/s

Open this example in the calculator and change any input.

Formula

\(P_n = P_0 (1 + r)^n, \quad Q_{avg} = \frac{P_n\, q}{1\ \text{day}}, \quad Q_{md} = k_d Q_{avg}, \quad Q_{ph} = k_h Q_{avg}\)

Variables

Symbol Meaning SI unit
\(P_0\) Present population -
\(r\) Annual growth rate -
\(n\) Design period (years) -
\(q\) Per capita supply (volume per person per day) m³
\(k_d\) Maximum day factor -
\(k_h\) Peak hour factor -
\(P_n\) Design population P₀(1 + r)ⁿ -
\(Q_{avg}\) Average daily demand m³/s
\(Q_{md}\) Maximum day demand m³/s
\(Q_{ph}\) Peak hour flow m³/s

Method and standards

Geometric growth and per capita demand.

Where it is used

  • Township and plant colony water supply.
  • Pump and main sizing.

Common mistakes

  • Linear growth for compounding.
  • Peak hour factor on maximum day.

Assumptions and limits

  • The per capita supply is a volume per person per day, entered in litres or US gallons (the page converts).

  • Steady growth rate.

References

  • Geometric growth population forecast; demand = population × per capita supply × peak factors

Questions and answers

5000 people growing 2 % a year for 30 years at 135 L/day?

9057 people, 1223 m³/day on average.

Where do peak factors come from?

Your water supply manual, by population size.

Plant colonies?

Add process, fire and gardening water separately.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.