Worked example
Example: 70 bar, 10 %. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Pressure (absolute) | 70.000 bar |
| Steam quality | 10.000 % |
| Chisholm constant: 20 tt, 12 vt, 10 tv, 5 vv (liquid–vapour; t turbulent, v viscous) | 20.000 - |
| Pressure drop of the liquid flowing alone | 2.0000 kPa |
| Total mass flux | 1,000.0 kg/(m²·s) |
| Tube inside diameter | 50.000 mm |
Applying the formula below gives:
| Result | Value |
|---|---|
| Martinelli parameter, in the form set by C | 1.8792 |
| Reynolds number of the liquid flowing alone | 493,063 |
| Reynolds number of the vapour flowing alone | 264,697 |
| Two-phase multiplier | 11.926 |
| Two-phase frictional pressure drop | 23.852 kPa |
Open this example in the calculator and change any input.
Formula
\(Re_l = \frac{G(1-x)D}{\mu_l}, \quad Re_v = \frac{G x D}{\mu_v}, \quad f = \frac{16}{Re} \text{ (viscous)} \text{ or } 0.046\,Re^{-0.2} \text{ (turbulent)}\)
\(X^2 = \frac{f_l}{f_v}\left(\frac{1-x}{x}\right)^2 \frac{\rho_v}{\rho_l}, \quad \phi_l^2 = 1 + \frac{C}{X} + \frac{1}{X^2}, \quad \Delta p_{tp} = \phi_l^2\,\Delta p_l\)
For both phases turbulent this is \(X_{tt} = \left(\frac{1-x}{x}\right)^{0.9}\left(\frac{\rho_v}{\rho_l}\right)^{0.5}\left(\frac{\mu_l}{\mu_v}\right)^{0.1}\).
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(p\) | Pressure (absolute) | Pa |
| \(x\) | Steam quality | - |
| \(C\) | Chisholm constant: 20 tt, 12 vt, 10 tv, 5 vv (liquid–vapour; t turbulent, v viscous) | - |
| \(G\) | Total mass flux | kg/(m²·s) |
| \(D\) | Tube inside diameter | m |
| \(\Delta p_l\) | Pressure drop of the liquid flowing alone | Pa |
| \(X\) | Martinelli parameter, in the form set by C | - |
| \(X_{tt}\) | X with both phases turbulent | - |
| \(Re_l\), \(Re_v\) | Reynolds numbers of the liquid and the vapour flowing alone | - |
| \(f\), \(f_l\), \(f_v\) | Fanning friction factor; of the liquid and of the vapour flowing alone | - |
| \(\rho_l\), \(\rho_v\) | Saturated liquid and vapour densities (IF97) | kg/m³ |
| \(\mu_l\), \(\mu_v\) | Saturated liquid and vapour viscosities (IAPWS 2008) | Pa·s |
| \(\phi_l^2\) | Two-phase multiplier | - |
| \(\Delta p_{tp}\) | Two-phase frictional pressure drop | Pa |
Method and standards
Lockhart–Martinelli separated-flow model with Chisholm's form of the liquid multiplier. The Martinelli parameter X is the square root of the ratio of the liquid-alone to the vapour-alone friction gradients, each with the viscous (16/Re) or turbulent (0.046 Re^−0.2) friction factor that the chosen C stands for, as Lockhart and Martinelli and Chisholm define it. Saturated-liquid and vapour properties from IAPWS-IF97 and IAPWS 2008. A note appears when the Reynolds numbers (viscous below 1000, turbulent above 2000) do not match the regime of C.
Where it is used
- Riser and evaporator pressure drop.
- Flashing lines.
Common mistakes
- Total flow used for the liquid-alone drop.
Assumptions and limits
- Separated-flow model.
- The form of X follows C (20, 12, 10 or 5); any other C uses the turbulent–turbulent form.
References
- Lockhart and Martinelli
- Chem. Eng. Prog. 45 (1949); Chisholm
- Int. J. Heat Mass Transfer 10 (1967): φ_l² = 1 + C/X + 1/X²; Collier and Thome
- Convective Boiling and Condensation; X_tt with IAPWS-IF97 densities and IAPWS 2008 viscosities
Questions and answers
What is Δp_l?
The friction loss if only the liquid fraction of the flow ran in the pipe.
Which C?
20 when both phases are turbulent; 12, 10 or 5 for the laminar combinations.
Accuracy?
Scatter of ±30 % or more is normal for two-phase friction correlations.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.