Worked example
Example: Drum 1 500 mm x 8 m, levels 600 to 750 mm, 70 bar(a), 50 t/h. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Drum inside diameter | 1,500.0 mm |
| Drum straight length | 8.0000 m |
| Lower level above the drum bottom (e.g. low-low trip) | 600.00 mm |
| Upper level above the drum bottom (e.g. normal water level, at most D) | 750.00 mm |
| Drum pressure (absolute) | 70.000 bar |
| Steaming rate | 50,000 kg/h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Holding time between the levels | 95.225 s |
| Water between the levels | 1,322.6 kg |
| Volume between the levels | 1.7879 m³ |
| Density of saturated water | 739.72 kg/m³ |
Open this example in the calculator and change any input.
Formula
\(A(h) = R^2\cos^{-1}\!\left(\frac{R-h}{R}\right) - (R-h)\sqrt{2Rh - h^2} \qquad R = \frac{D}{2}\)
\(V = L\,[A(h_2) - A(h_1)] \qquad m = \rho\,V \qquad t_h = \frac{m}{\dot m_s}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(D\) | drum inside diameter | m |
| \(L\) | drum straight length | m |
| \(h_1\) | lower level above the drum bottom | m |
| \(h_2\) | upper level above the drum bottom | m |
| \(p\) | drum pressure, absolute | Pa |
| \(\dot m_s\) | steaming rate | kg/s |
| \(t_h\) | holding time between the levels | s |
| \(m\) | water between the levels | kg |
| \(V\) | volume between the levels | m³ |
| \(\rho\) | density of saturated water | kg/m³ |
| \(A(h)\) | area of the circular segment up to level \(h\) | m² |
Method and standards
Volume of a horizontal cylinder between two liquid levels (circular segments) times the density of saturated water from FireCAD's IAPWS-IF97.
Where it is used
- Sizing steam drums of water-tube boilers.
- Checking response time to feed interruptions.
- Setting drum level alarm margins.
Common mistakes
- Using total drum volume instead of the volume between levels.
- Ignoring swell and shrink.
- Using cold-water density.
Assumptions and limits
- Dished ends and drum internals are ignored (ends add a little, internals take a little).
- Steady steaming rate with no feedwater and no blowdown.
- Steam bubbles below the surface (swell) reduce the real water content.
References
- Geometry of a horizontal cylinder
- IAPWS R7-97(2012) IF97 (saturated water density)
Questions and answers
How long does a drum last without feedwater?
Water between the levels ÷ steaming rate. A 1 500 mm × 8 m drum at 70 bar(a) holds 1.79 m³ (1 323 kg) between 600 and 750 mm; at 50 t/h that is 95 seconds.
Why is the density so low?
Drum water is at saturation: 740 kg/m³ at 70 bar(a), 672 kg/m³ at 110 bar(a).
Is the water in the tubes counted?
No, only the drum between the two levels. Swell and shrink on load changes and the water in risers and downcomers change the real time.
Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.