Chiller COP versus Lift: Condensing Temperature Effect

Carnot fraction of a chiller from its COP at one evaporating and condensing temperature, the COP at another condensing temperature and power per kelvin.

Process steam and utilitiesChemical and fertiliserFood, dairy and textile

Inputs

Examples: Illustrative 36 to 30 C condensingFouled condenser +3 KLow-temperature plant

Accepted: 0.5 to 15
Accepted: -43.15 to 26.85 °C
Accepted: 6.85 to 66.85 °C
Accepted: 6.85 to 66.85 °C

Results

Holding the Carnot fraction constant, COP = η_C·T_e/(T_c − T_e). Real chillers stay close to this over moderate changes; each kelvin of lower condensing temperature (cooler condenser water, clean tubes) typically saves 2–3 % of compressor power. Use the maker's curves for large changes or variable-speed machines.

Carnot fraction62.332%
COP at the new condensing temperature5.4375
Compressor power change for the same duty10.345%
Power change per kelvin of condensing temperature3.4483%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 36 to 30 C condensing. The inputs, in the units selected above:

InputValue
Known COP5.5000 -
Evaporating temperature5.0000 °C
Condensing temperature for the known COP36.000 °C
New condensing temperature30.000 °C

Applying the formula below gives:

ResultValue
Carnot fraction61.298 %
COP at the new condensing temperature6.8200
Compressor power change for the same duty-19.355 %
Power change per kelvin of condensing temperature3.2258 %

Open this example in the calculator and change any input.

Formula

\(\eta_C = COP_0\frac{T_{c,0} - T_e}{T_e}, \quad COP_1 = \eta_C\frac{T_e}{T_{c,1} - T_e}\)

Variables

Symbol Meaning SI unit
\(COP_0\) Known COP -
\(T_e\) Evaporating temperature K
\(T_{c,0}\) Condensing temperature for the known COP K
\(T_{c,1}\) New condensing temperature K
\(\eta_C\) Carnot fraction -
\(COP_1\) COP at the new condensing temperature -
\(\Delta P/P_0\) Compressor power change for the same duty -
\(\Delta P/\Delta T\) Power change per kelvin of condensing temperature -

Method and standards

Lift and COP.

Where it is used

  • Condenser water reset and cooling tower savings.
  • Fouling cost estimates.

Common mistakes

  • Using Celsius temperatures in the ratio.
  • Extrapolating far outside the rated conditions.

Assumptions and limits

  • Constant Carnot fraction; same duty and evaporating temperature.

References

  • Constant Carnot-fraction COP model

Questions and answers

Why does lift matter so much?

Compressor work rises with the temperature difference between condensing and evaporating; halving lift roughly doubles the ideal COP.

How can lift be reduced?

Colder condenser water, warmer chilled water, clean tubes and good approaches on both heat exchangers.

What do the defaults represent?

An illustrative chiller with COP 5.5 at 5 °C evaporating and 36 °C condensing, checked at 30 °C condensing.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Stoecker and Jones, Refrigeration and Air Conditioning, 2nd ed. (McGraw-Hill, 1982)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.