Worked example
Example: Illustrative 36 to 30 C condensing. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Known COP | 5.5000 - |
| Evaporating temperature | 5.0000 °C |
| Condensing temperature for the known COP | 36.000 °C |
| New condensing temperature | 30.000 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Carnot fraction | 61.298 % |
| COP at the new condensing temperature | 6.8200 |
| Compressor power change for the same duty | -19.355 % |
| Power change per kelvin of condensing temperature | 3.2258 % |
Open this example in the calculator and change any input.
Formula
\(\eta_C = COP_0\frac{T_{c,0} - T_e}{T_e}, \quad COP_1 = \eta_C\frac{T_e}{T_{c,1} - T_e}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(COP_0\) | Known COP | - |
| \(T_e\) | Evaporating temperature | K |
| \(T_{c,0}\) | Condensing temperature for the known COP | K |
| \(T_{c,1}\) | New condensing temperature | K |
| \(\eta_C\) | Carnot fraction | - |
| \(COP_1\) | COP at the new condensing temperature | - |
| \(\Delta P/P_0\) | Compressor power change for the same duty | - |
| \(\Delta P/\Delta T\) | Power change per kelvin of condensing temperature | - |
Method and standards
Lift and COP.
Where it is used
- Condenser water reset and cooling tower savings.
- Fouling cost estimates.
Common mistakes
- Using Celsius temperatures in the ratio.
- Extrapolating far outside the rated conditions.
Assumptions and limits
- Constant Carnot fraction; same duty and evaporating temperature.
References
- Constant Carnot-fraction COP model
Questions and answers
Why does lift matter so much?
Compressor work rises with the temperature difference between condensing and evaporating; halving lift roughly doubles the ideal COP.
How can lift be reduced?
Colder condenser water, warmer chilled water, clean tubes and good approaches on both heat exchangers.
What do the defaults represent?
An illustrative chiller with COP 5.5 at 5 °C evaporating and 36 °C condensing, checked at 30 °C condensing.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.