Transformer Reactive Power and Fixed Capacitor Compensation

Reactive power a transformer draws at no load and at a loading, from its no-load current and impedance, and the fixed capacitor for its no-load magnetising kvar.

Inputs

Examples: Illustrative 1000 kVA at 75 % load250 kVA, light load2500 kVA, full load

Accepted: 10 to 1,000,000 kVA
Accepted: 0.1 to 10 %
Accepted: 1 to 25 %
Accepted: 0 to 150 %

Results

A transformer draws magnetising reactive power i₀·S all the time it is energised, and leakage reactive power u_k·β²·S that grows with the square of the load (taking the impedance as reactive, close for large units). Where the tariff meters on the high-voltage side, a fixed capacitor of about the no-load kvar on the secondary compensates the magnetising part; the load part is compensated with the load. Too large a fixed capacitor raises light-load voltage and can resonate with harmonics.

No-load reactive power (fixed capacitor)15.000kvar
Leakage reactive power at the load28.125kvar
Total reactive power of the transformer43.125kvar

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 1000 kVA at 75 % load. The inputs, in the units selected above:

InputValue
Transformer rating1,000.0 kVA
No-load current (share of rated)1.5000 %
Impedance voltage5.0000 %
Load as a share of rating75.000 %

Applying the formula below gives:

ResultValue
No-load reactive power (fixed capacitor)15.000 kvar
Leakage reactive power at the load28.125 kvar
Total reactive power of the transformer43.125 kvar

Open this example in the calculator and change any input.

Formula

\(Q_0 = i_0 S, \quad Q_L = u_k\beta^2 S\)

Variables

Symbol Meaning SI unit
\(S\) Transformer rating VA
\(i_0\) No-load current (share of rated) -
\(u_k\) Impedance voltage -
\(\beta\) Load as a share of rating -
\(Q_0\) No-load reactive power (fixed capacitor) var
\(Q_L\) Leakage reactive power at the load var
\(Q_T\) Total reactive power of the transformer var

Method and standards

Transformer compensation.

Where it is used

  • Utility HT metering compliance.
  • Distribution transformer power factor.

Common mistakes

  • Oversizing the fixed capacitor.
  • Ignoring harmonic resonance.

Assumptions and limits

  • Impedance mostly reactive.

References

  • Transformer reactive power from no-load current and impedance

Questions and answers

What fixed capacitor suits a 1,000 kVA transformer with 1.5 % no-load current?

About 15 kvar.

How much reactive power does it draw at 75 % load?

About 28 kvar of leakage reactive power at 5 % impedance, 43 kvar in all.

What do the defaults represent?

An illustrative 1,000 kVA transformer with 1.5 % no-load current and 5 % impedance at 75 % load.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.