Worked example
Example: Illustrative 0.27 mm GO steel core at 50 Hz, 1.5 T. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Frequency | 50.000 Hz |
| Peak flux density | 1.5000 T |
| Hysteresis coefficient (W/kg at 1 Hz, 1 T) | 0.012000 - |
| Steinmetz exponent | 1.8000 - |
| Lamination thickness | 0.27000 mm |
| Steel resistivity | 48.000 µΩ·cm |
| Steel density | 7,650.0 kg/m³ |
| Core mass | 450.00 kg |
Applying the formula below gives:
| Result | Value |
|---|---|
| Hysteresis loss (W/kg) | 1.2448 |
| Classical eddy current loss (W/kg) | 0.18369 |
| Total specific core loss (W/kg) | 1.4285 |
| Core loss of the whole core | 642.84 W |
Open this example in the calculator and change any input.
Formula
\(p_h = k_hf\hat B^n, \quad p_e = \frac{\pi^2d^2f^2\hat B^2}{6\rho_e\rho_m}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(f\) | Frequency | 1/s |
| \(\hat B\) | Peak flux density | T |
| \(k_h\) | Hysteresis coefficient (W/kg at 1 Hz, 1 T) | - |
| \(n\) | Steinmetz exponent | - |
| \(d\) | Lamination thickness | m |
| \(\rho_e\) | Steel resistivity | Ω·m |
| \(\rho_m\) | Steel density | kg/m³ |
| \(m\) | Core mass | kg |
| \(p_h\) | Hysteresis loss (W/kg) | - |
| \(p_e\) | Classical eddy current loss (W/kg) | - |
| \(p\) | Total specific core loss (W/kg) | - |
| \(P_{core}\) | Core loss of the whole core | W |
Method and standards
Core loss.
Where it is used
- Transformer and motor core loss estimates.
- Comparing lamination grades and thicknesses.
Common mistakes
- Using RMS flux density instead of peak.
- Applying the classical eddy term to thick or solid cores (skin effect).
Assumptions and limits
- Sinusoidal flux; lamination thin compared with the skin depth.
References
- Steinmetz hysteresis law and classical eddy current loss
Questions and answers
Why does loss rise faster than frequency?
Eddy current loss grows with the square of frequency, hysteresis loss only linearly.
Why is measured loss higher than the sum?
Domain wall motion adds an excess loss not captured by the classical eddy formula.
What do the defaults represent?
An illustrative grain-oriented 0.27 mm transformer steel core of 450 kg at 50 Hz and 1.5 T.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Chapman, Electric Machinery Fundamentals, 5th ed. (McGraw-Hill, 2012)