Worked example
Example: Illustrative 600-turn winding, 0.8 T remanence. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Turns of the energised winding | 600.00 - |
| Winding height | 1,000.0 mm |
| Rated peak flux density | 1.7000 T |
| Remanent flux density | 0.80000 T |
| Saturation flux density of the core | 2.0300 T |
| Rated rms current of that winding | 105.00 A |
Applying the formula below gives:
| Result | Value |
|---|---|
| Peak flux demanded | 4.2000 T |
| Flux beyond saturation | 2.1700 T |
| Peak inrush current | 2,878.1 A |
| Multiple of rated peak current | 19.382 |
Open this example in the calculator and change any input.
Formula
\(B_{pk} = 2B_n + B_r, \quad i_{pk} \approx \frac{h_w(2B_n + B_r - B_s)}{\mu_0N}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(N\) | Turns of the energised winding | - |
| \(h_w\) | Winding height | m |
| \(B_n\) | Rated peak flux density | T |
| \(B_r\) | Remanent flux density | T |
| \(B_s\) | Saturation flux density of the core | T |
| \(I_r\) | Rated rms current of that winding | A |
| \(B_{pk}\) | Peak flux demanded | T |
| \(\Delta B\) | Flux beyond saturation | T |
| \(i_{pk}\) | Peak inrush current | A |
| \(i_{pk}/(\sqrt2I_r)\) | Multiple of rated peak current | - |
Method and standards
Inrush estimate.
Where it is used
- Protection settings and fuse selection.
- Voltage dip studies when energising transformers.
Common mistakes
- Ignoring source impedance for small transformers on weak supplies.
- Assuming zero remanence after a test.
Assumptions and limits
- Single phase, worst-case switching instant; resistance and source impedance neglected.
References
- Air-core saturation estimate of inrush
Questions and answers
Why is inrush worst at voltage zero?
Flux must start a full positive half cycle from the remanent value, reaching about twice the normal peak.
How is inrush told apart from a fault by protection?
Inrush is rich in second harmonic; differential relays block on it, typically above 15–20 % of fundamental.
What do the defaults represent?
An illustrative winding of 600 turns, 1 m high, rated at 1.7 T with 0.8 T remanence, core saturating at 2.03 T, rated 105 A.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Bertagnolli, Short-Circuit Duty of Power Transformers (ABB, 1996), Kulkarni and Khaparde, Transformer Engineering: Design, Technology and Diagnostics, 2nd ed. (CRC, 2012)