Transformer Total Owning Cost (Loss Capitalisation)

Loss capitalisation factors A and B and total owning cost of a transformer from price, no-load and load losses, energy price, loading, discount rate and life.

Thermal power plantProcess steam and utilities

Inputs

Examples: Illustrative 1600 kVAAmorphous core low no-loadHeavily loaded industrial 80 %

Accepted: 0 to 1E+9
Accepted: 0.001 to 1,000 kW
Accepted: 0.001 to 10,000 kW
Accepted: 0 to 1
Accepted: 0 to 150 %
Accepted: 0 to 30 %
Accepted: 1 to 60

Results

TOC = price + A·P₀ + B·P_k with A = c_e·8,760·PWF and B = A·k², k being the rms load ratio (load losses go with load squared). Utilities often set A and B by policy, including demand charges; enter those to compare offers.

Present-worth factor12.409
No-load loss factor (per kW)10,870
Load loss factor (per kW)2,717.6
Total owning cost100,492
Loss energy per year32.631MWh
Share of losses in owning cost40.294%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 1600 kVA. The inputs, in the units selected above:

InputValue
Purchase price60,000 -
No-load loss1.1000 kW
Load loss at rated load10.500 kW
Energy price (per kWh)0.10000 -
Average load ratio (rms load over rating)50.000 %
Discount rate7.0000 %
Life (years)30.000 -

Applying the formula below gives:

ResultValue
Present-worth factor12.409
No-load loss factor (per kW)10,870
Load loss factor (per kW)2,717.6
Total owning cost100,492
Loss energy per year32.631 MWh
Share of losses in owning cost40.294 %

Open this example in the calculator and change any input.

Formula

\(TOC = C_0 + AP_0 + BP_k, \quad A = c_e\cdot 8760\cdot PWF, \quad B = Ak^2\)

Variables

Symbol Meaning SI unit
\(C_0\) Purchase price -
\(P_0\) No-load loss W
\(P_k\) Load loss at rated load W
\(c_e\) Energy price (per kWh) -
\(k\) Average load ratio (rms load over rating) -
\(i\) Discount rate -
\(n\) Life (years) -
\(PWF\) Present-worth factor -
\(A\) No-load loss factor (per kW) -
\(B\) Load loss factor (per kW) -
\(TOC\) Total owning cost -
\(E_L\) Loss energy per year J
\((AP_0 + BP_k)/TOC\) Share of losses in owning cost -

Method and standards

Loss capitalisation.

Where it is used

  • Transformer tender evaluation.
  • Efficiency upgrade cases.

Common mistakes

  • Using average instead of rms load for B.
  • Ignoring demand charges on peak losses.

Assumptions and limits

  • Constant energy price and loading.

References

  • Loss capitalisation (total owning cost)

Questions and answers

Why is a cheaper transformer often dearer?

Over 30 years the cost of its losses can exceed its purchase price several times; low-loss designs win on total owning cost.

Why is A larger than B?

No-load loss runs every hour regardless of load, while load loss scales with the square of loading, which is usually well below rated.

What do the defaults represent?

An illustrative 1,600 kVA distribution transformer at 60,000, 1.1 kW no-load and 10.5 kW load loss, energy at 0.10 per kWh, 50 % rms loading, 7 % over 30 years.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Gilbert Masters, Renewable and Efficient Electric Power Systems (Wiley, 2004), ch. 3

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.