Worked example
Example: Illustrative 1600 kVA. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Purchase price | 60,000 - |
| No-load loss | 1.1000 kW |
| Load loss at rated load | 10.500 kW |
| Energy price (per kWh) | 0.10000 - |
| Average load ratio (rms load over rating) | 50.000 % |
| Discount rate | 7.0000 % |
| Life (years) | 30.000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Present-worth factor | 12.409 |
| No-load loss factor (per kW) | 10,870 |
| Load loss factor (per kW) | 2,717.6 |
| Total owning cost | 100,492 |
| Loss energy per year | 32.631 MWh |
| Share of losses in owning cost | 40.294 % |
Open this example in the calculator and change any input.
Formula
\(TOC = C_0 + AP_0 + BP_k, \quad A = c_e\cdot 8760\cdot PWF, \quad B = Ak^2\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(C_0\) | Purchase price | - |
| \(P_0\) | No-load loss | W |
| \(P_k\) | Load loss at rated load | W |
| \(c_e\) | Energy price (per kWh) | - |
| \(k\) | Average load ratio (rms load over rating) | - |
| \(i\) | Discount rate | - |
| \(n\) | Life (years) | - |
| \(PWF\) | Present-worth factor | - |
| \(A\) | No-load loss factor (per kW) | - |
| \(B\) | Load loss factor (per kW) | - |
| \(TOC\) | Total owning cost | - |
| \(E_L\) | Loss energy per year | J |
| \((AP_0 + BP_k)/TOC\) | Share of losses in owning cost | - |
Method and standards
Loss capitalisation.
Where it is used
- Transformer tender evaluation.
- Efficiency upgrade cases.
Common mistakes
- Using average instead of rms load for B.
- Ignoring demand charges on peak losses.
Assumptions and limits
- Constant energy price and loading.
References
- Loss capitalisation (total owning cost)
Questions and answers
Why is a cheaper transformer often dearer?
Over 30 years the cost of its losses can exceed its purchase price several times; low-loss designs win on total owning cost.
Why is A larger than B?
No-load loss runs every hour regardless of load, while load loss scales with the square of loading, which is usually well below rated.
What do the defaults represent?
An illustrative 1,600 kVA distribution transformer at 60,000, 1.1 kW no-load and 10.5 kW load loss, energy at 0.10 per kWh, 50 % rms loading, 7 % over 30 years.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Gilbert Masters, Renewable and Efficient Electric Power Systems (Wiley, 2004), ch. 3