Worked example
Example: Illustrative copper winding heat run. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Conductor material | Copper (k = 234.5) |
| Cold resistance | 0.45200 Ω |
| Winding temperature at cold measurement | 20.000 °C |
| Hot resistance at shutdown | 0.57100 Ω |
| Cooling medium temperature at the end of the test | 30.000 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Average hot winding temperature | 87.003 °C |
| Winding temperature rise | 57.003 K |
| Resistance ratio | 1.2633 |
Open this example in the calculator and change any input.
Formula
\(T_2 = \frac{R_2}{R_1}(T_1 + k) - k, \quad \Delta T_w = T_2 - T_a\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\text{conductor}\) | Conductor material | - |
| \(R_1\) | Cold resistance | Ω |
| \(T_1\) | Winding temperature at cold measurement | K |
| \(R_2\) | Hot resistance at shutdown | Ω |
| \(T_a\) | Cooling medium temperature at the end of the test | K |
| \(T_2\) | Average hot winding temperature | K |
| \(\Delta T_w\) | Winding temperature rise | K |
| \(R_2/R_1\) | Resistance ratio | - |
Method and standards
Resistance method.
Where it is used
- Transformer and motor heat-run tests.
- Checking overload temperature in service.
Common mistakes
- Measuring cold resistance before the winding reaches ambient.
- Using the copper constant for aluminium.
Assumptions and limits
- Uniform winding temperature change; linear resistance-temperature relation.
References
- Resistance method of temperature rise
Questions and answers
Why 234.5 for copper?
Copper's resistance extrapolates to zero at about −234.5 °C, so resistance is proportional to T + 234.5.
Why extrapolate to shutdown?
The winding cools quickly once power is removed; readings over the first minutes are extrapolated back to zero time.
What do the defaults represent?
An illustrative copper winding measuring 0.452 Ω cold at 20 °C and 0.571 Ω hot, with 30 °C cooling air at the end of the run.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Harlow (ed.), Electric Power Transformer Engineering, 3rd ed. (CRC, 2012)