Worked example
Example: Illustrative 1000 kVA at 75 % load. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Transformer rating | 1,000.0 kVA |
| No-load current (share of rated) | 1.5000 % |
| Impedance voltage | 5.0000 % |
| Load as a share of rating | 75.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| No-load reactive power (fixed capacitor) | 15.000 kvar |
| Leakage reactive power at the load | 28.125 kvar |
| Total reactive power of the transformer | 43.125 kvar |
Open this example in the calculator and change any input.
Formula
\(Q_0 = i_0 S, \quad Q_L = u_k\beta^2 S\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(S\) | Transformer rating | VA |
| \(i_0\) | No-load current (share of rated) | - |
| \(u_k\) | Impedance voltage | - |
| \(\beta\) | Load as a share of rating | - |
| \(Q_0\) | No-load reactive power (fixed capacitor) | var |
| \(Q_L\) | Leakage reactive power at the load | var |
| \(Q_T\) | Total reactive power of the transformer | var |
Method and standards
Transformer compensation.
Where it is used
- Utility HT metering compliance.
- Distribution transformer power factor.
Common mistakes
- Oversizing the fixed capacitor.
- Ignoring harmonic resonance.
Assumptions and limits
- Impedance mostly reactive.
References
- Transformer reactive power from no-load current and impedance
Questions and answers
What fixed capacitor suits a 1,000 kVA transformer with 1.5 % no-load current?
About 15 kvar.
How much reactive power does it draw at 75 % load?
About 28 kvar of leakage reactive power at 5 % impedance, 43 kvar in all.
What do the defaults represent?
An illustrative 1,000 kVA transformer with 1.5 % no-load current and 5 % impedance at 75 % load.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.