Worked example
Example: Illustrative 2.18 kW array on 48 V. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Module short-circuit current | 11.000 A |
| Strings in parallel | 2.0000 - |
| Module open-circuit voltage | 49.000 V |
| Modules in series per string | 2.0000 - |
| Array rated power | 2.1800 kW |
| Battery bank voltage | 48.000 V |
| Safety factor on current | 1.2500 - |
| Cold-temperature factor on V_oc | 1.1200 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| PWM controller rating | 27.500 A |
| MPPT controller output rating | 56.771 A |
| Maximum array open-circuit voltage (cold) | 109.76 V |
| Array short-circuit current | 22.000 A |
Open this example in the calculator and change any input.
Formula
\(I_{PWM} = k_sN_pI_{sc}, \quad I_{MPPT} = k_s\frac{P_a}{V_b}, \quad V_{max} = k_TN_sV_{oc}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(I_{sc}\) | Module short-circuit current | A |
| \(N_p\) | Strings in parallel | - |
| \(V_{oc}\) | Module open-circuit voltage | V |
| \(N_s\) | Modules in series per string | - |
| \(P_a\) | Array rated power | W |
| \(V_b\) | Battery bank voltage | V |
| \(k_s\) | Safety factor on current | - |
| \(k_T\) | Cold-temperature factor on V_oc | - |
| \(I_{PWM}\) | PWM controller rating | A |
| \(I_{MPPT}\) | MPPT controller output rating | A |
| \(V_{max}\) | Maximum array open-circuit voltage (cold) | V |
| \(I_a\) | Array short-circuit current | A |
Method and standards
Charge controller.
Where it is used
- Off-grid and hybrid solar systems.
- Solar water pumping with batteries.
Common mistakes
- Sizing an MPPT on short-circuit current.
- Ignoring cold-weather V_oc.
Assumptions and limits
- Rated module values; margin as entered.
References
- Charge controller sizing from array current
- power and voltage
Questions and answers
What controller suits a 2.18 kW array on a 48 V battery?
An MPPT rated about 57 A (2,180/48 × 1.25), accepting at least 110 V input.
When is PWM enough?
For small systems with modules matched to the battery voltage.
What do the defaults represent?
An illustrative array of four 545 W modules (11 A I_sc, 49 V V_oc), two in series and two strings in parallel, on a 48 V battery.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.