FireCADCalc

Solar Charge Controller Sizing (PWM and MPPT)

Current rating of a PWM or MPPT solar charge controller from array short-circuit current or power and battery voltage, and the cold open-circuit voltage.

Inputs

Examples: Illustrative 2.18 kW array on 48 VSmall 12 V PWM system24 V MPPT, three strings

Accepted: 0.1 to 50 A
Accepted: 1 to 100
Accepted: 1 to 100 V
Accepted: 1 to 50
Accepted: 0.01 to 1,000 kW
Accepted: 6 to 1,000 V
Accepted: 1 to 2
Accepted: 1 to 1.3

Results

A PWM controller connects the array directly to the battery, so it must carry the array's short-circuit current with a margin (about 1.25), and the array's maximum-power voltage should be only a little above the battery's. An MPPT controller converts the array power to battery voltage, so its output current is about P/V_battery with the same margin, and it can take a higher-voltage array. In both cases the cold-morning open-circuit voltage (V_oc raised by roughly 0.3 % per °C below 25 °C) must stay below the controller's maximum input voltage.

The string voltage is far above the battery voltage: use an MPPT controller; a PWM controller would waste much of the power.

PWM controller rating48.750A
MPPT controller output rating234.38A
Maximum array open-circuit voltage (cold)155.25V
Array short-circuit current39.000A

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 2.18 kW array on 48 V. The inputs, in the units selected above:

InputValue
Module short-circuit current11.000 A
Strings in parallel2.0000 -
Module open-circuit voltage49.000 V
Modules in series per string2.0000 -
Array rated power2.1800 kW
Battery bank voltage48.000 V
Safety factor on current1.2500 -
Cold-temperature factor on V_oc1.1200 -

Applying the formula below gives:

ResultValue
PWM controller rating27.500 A
MPPT controller output rating56.771 A
Maximum array open-circuit voltage (cold)109.76 V
Array short-circuit current22.000 A

Open this example in the calculator and change any input.

Formula

\(I_{PWM} = k_sN_pI_{sc}, \quad I_{MPPT} = k_s\frac{P_a}{V_b}, \quad V_{max} = k_TN_sV_{oc}\)

Variables

Symbol Meaning SI unit
\(I_{sc}\) Module short-circuit current A
\(N_p\) Strings in parallel -
\(V_{oc}\) Module open-circuit voltage V
\(N_s\) Modules in series per string -
\(P_a\) Array rated power W
\(V_b\) Battery bank voltage V
\(k_s\) Safety factor on current -
\(k_T\) Cold-temperature factor on V_oc -
\(I_{PWM}\) PWM controller rating A
\(I_{MPPT}\) MPPT controller output rating A
\(V_{max}\) Maximum array open-circuit voltage (cold) V
\(I_a\) Array short-circuit current A

Method and standards

Charge controller.

Where it is used

  • Off-grid and hybrid solar systems.
  • Solar water pumping with batteries.

Common mistakes

  • Sizing an MPPT on short-circuit current.
  • Ignoring cold-weather V_oc.

Assumptions and limits

  • Rated module values; margin as entered.

References

  • Charge controller sizing from array current
  • power and voltage

Questions and answers

What controller suits a 2.18 kW array on a 48 V battery?

An MPPT rated about 57 A (2,180/48 × 1.25), accepting at least 110 V input.

When is PWM enough?

For small systems with modules matched to the battery voltage.

What do the defaults represent?

An illustrative array of four 545 W modules (11 A I_sc, 49 V V_oc), two in series and two strings in parallel, on a 48 V battery.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators