Worked example
Example: Eight 12 V 150 Ah: 4 in series, 2 strings. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Voltage of one battery or cell | 12.000 V |
| Capacity of one battery | 150.00 Ah |
| Batteries in series per string | 4.0000 - |
| Strings in parallel | 2.0000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Bank voltage | 48.000 V |
| Bank capacity | 300.00 Ah |
| Stored energy (nominal) | 14.400 kWh |
| Batteries in the bank | 8.0000 |
Open this example in the calculator and change any input.
Formula
\(V = n_s V_b, \quad C = n_p C_b, \quad E = V\, C\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V_b\) | Voltage of one battery or cell | V |
| \(C_b\) | Capacity of one battery | C |
| \(n_s\) | Batteries in series per string | - |
| \(n_p\) | Strings in parallel | - |
| \(V\) | Bank voltage | V |
| \(C\) | Bank capacity | C |
| \(E\) | Stored energy (nominal) | J |
| \(n\) | Batteries in the bank | - |
Method and standards
Series and parallel combination of identical batteries.
Where it is used
- Solar, UPS and telecom banks.
- Inverter battery planning.
Common mistakes
- Mixing old and new batteries.
- Counting Ah of series batteries twice.
Assumptions and limits
- Identical batteries.
- Numbers in series and in parallel are rounded to whole numbers, with a note.
References
- Kirchhoff's circuit laws (series voltages add, parallel currents add)
Questions and answers
What do eight 12 V 150 Ah batteries give as 4 in series, 2 strings?
48 V, 300 Ah, 14.4 kWh nominal.
Is all of that usable?
No: depth-of-discharge limits and the discharge rate reduce it.
Why avoid many parallel strings?
They share current unevenly; fewer, larger cells are better.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.