Worked example
Example: Illustrative home 12000 kWh. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Annual electricity consumption | 12,000 kWh |
| Share of consumption to cover | 100.00 % |
| Specific yield (kWh per kWp per year) | 1,450.0 - |
| Module rating | 0.43000 kW |
| Module area | 1.9500 m² |
| Roof area factor (gaps, access; 1.1–1.3) | 1.2000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| PV capacity needed | 8.2759 kW |
| Modules | 20.000 |
| Installed with whole modules | 8.6000 kW |
| Roof area needed | 46.800 m² |
| Annual PV generation | 12.470 MWh |
Open this example in the calculator and change any input.
Formula
\(P_{PV} = \frac{fE}{Y}, \quad n = \left\lceil\frac{P_{PV}}{P_m}\right\rceil, \quad A = nA_mk_A\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(E\) | Annual electricity consumption | J |
| \(f\) | Share of consumption to cover | - |
| \(Y\) | Specific yield (kWh per kWp per year) | - |
| \(P_m\) | Module rating | W |
| \(A_m\) | Module area | m² |
| \(k_A\) | Roof area factor (gaps, access; 1.1–1.3) | - |
| \(P_{PV}\) | PV capacity needed | W |
| \(n\) | Modules | - |
| \(P\) | Installed with whole modules | W |
| \(A\) | Roof area needed | m² |
| \(E_{PV}\) | Annual PV generation | J |
Method and standards
PV sizing by annual energy.
Where it is used
- Home and commercial PV proposals.
- Net-zero building checks.
Common mistakes
- Using peak sun hours of one month as the annual yield.
- Ignoring shading and orientation in the yield.
Assumptions and limits
- Annual energy balance only.
References
- Annual energy balance for PV sizing
Questions and answers
How big a system covers a typical home?
About 1 kWp per 1,000–1,600 kWh a year depending on sunshine: 12,000 kWh needs about 8 kWp at 1,450 kWh/kWp.
Does covering the annual total make a home self-sufficient?
No: summer surplus is exported and winter evenings are imported; self-sufficiency is usually 30–40 % without a battery.
What do the defaults represent?
An illustrative home using 12,000 kWh a year, fully covered, at a specific yield of 1,450 kWh/kWp with 430 W, 1.95 m² modules.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Gilbert Masters, Renewable and Efficient Electric Power Systems (Wiley, 2004), ch. 9