PV Self-Consumption and Self-Sufficiency with a Battery

Daily PV self-consumption, self-sufficiency, battery use and grid import and export of a home or building from PV energy, day and night loads and battery size.

Thermal power plant

Inputs

Examples: Illustrative 25 kWh PV, 10 + 12 kWh load, 10 kWh batteryWinter day 8 kWh PVLarge battery 20 kWh, small night load

Accepted: 0 to 27,778 kWh
Accepted: 0 to 27,778 kWh
Accepted: 0 to 27,778 kWh
Accepted: 0 to 27,778 kWh
Accepted: 50 to 100 %

Results

Daily energy balance: PV first serves the coincident load, the surplus charges the battery (only as much as the evening load can use), the rest is exported. Usable capacity is split as √η on charge and discharge. Hourly profiles and cloudy days lower real self-sufficiency.

PV used directly10.000kWh
PV stored in the battery10.541kWh
Energy from the battery9.4868kWh
PV exported4.4591kWh
Grid import2.5132kWh
Self-consumption ratio82.164%
Self-sufficiency88.577%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 25 kWh PV, 10 + 12 kWh load, 10 kWh battery. The inputs, in the units selected above:

InputValue
PV energy per day25.000 kWh
Load during PV hours per day10.000 kWh
Load outside PV hours per day12.000 kWh
Usable battery capacity10.000 kWh
Battery round-trip efficiency90.000 %

Applying the formula below gives:

ResultValue
PV used directly10.000 kWh
PV stored in the battery10.541 kWh
Energy from the battery9.4868 kWh
PV exported4.4591 kWh
Grid import2.5132 kWh
Self-consumption ratio82.164 %
Self-sufficiency88.577 %

Open this example in the calculator and change any input.

Formula

\(E_{direct} = \min(E_{PV}, E_{day}), \quad E_{bat,out} = \min\left(\eta E_{bat,in}, E_{night}\right), \quad SS = \frac{E_{direct} + E_{bat,out}}{E_{day} + E_{night}}\)

Variables

Symbol Meaning SI unit
\(E_{PV}\) PV energy per day J
\(E_{day}\) Load during PV hours per day J
\(E_{night}\) Load outside PV hours per day J
\(C\) Usable battery capacity J
\(\eta\) Battery round-trip efficiency -
\(E_{direct}\) PV used directly J
\(E_{bat,in}\) PV stored in the battery J
\(E_{bat,out}\) Energy from the battery J
\(E_{export}\) PV exported J
\(E_{import}\) Grid import J
\(SC\) Self-consumption ratio -
\(SS\) Self-sufficiency -

Method and standards

PV-battery energy balance.

Where it is used

  • Home and commercial PV-battery sizing.
  • Tariff and export planning.

Common mistakes

  • Counting exported PV as self-consumed.
  • Sizing the battery for the PV surplus rather than the night load.

Assumptions and limits

  • One representative day; battery empty at sunrise.

References

  • Daily energy balance of PV with storage

Questions and answers

What is the difference between self-consumption and self-sufficiency?

Self-consumption is the share of PV used on site; self-sufficiency is the share of the load met by PV. A large PV system has high self-sufficiency but low self-consumption.

How big should a home battery be?

About the evening and night load it can cover from the daily surplus; beyond that extra capacity sits unused most days.

What do the defaults represent?

An illustrative home: 25 kWh of PV a day, 10 kWh used while the sun shines, 12 kWh in the evening and night, and a 10 kWh battery at 90 % round trip.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Gilbert Masters, Renewable and Efficient Electric Power Systems (Wiley, 2004), ch. 9

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.