Battery Wear Cost per kWh Throughput

Battery degradation (wear) cost and total cost per kWh delivered from pack cost, cycle life, depth of discharge, average capacity over life and charging price.

Thermal power plant

Inputs

Examples: Illustrative LFP 250/kWh, 6000 cyclesNMC 200/kWh, 2000 cyclesLead-acid 150/kWh, 800 cycles 50 %

Accepted: 1 to 5,000
Accepted: 10 to 50,000
Accepted: 5 to 100 %
Accepted: 50 to 100 %
Accepted: 50 to 100 %
Accepted: 0 to 1

Results

Wear cost = C_b/(N·DoD·f_avg); total = wear + charging price/η. Cycle life falls at higher depth of discharge and temperature; use the maker's cycle-life curve at the planned DoD. Financing and calendar ageing are not included.

Lifetime energy delivered per kWh of capacity (kWh)4,860.0
Wear cost per kWh delivered0.051440
Charging cost per kWh delivered0.055556
Total cost per kWh delivered0.10700

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative LFP 250/kWh, 6000 cycles. The inputs, in the units selected above:

InputValue
Battery pack cost (per kWh of capacity)250.00 -
Cycle life to end of life6,000.0 -
Depth of discharge per cycle90.000 %
Average capacity over life (fraction of new)90.000 %
Round-trip efficiency90.000 %
Charging energy price (per kWh)0.050000 -

Applying the formula below gives:

ResultValue
Lifetime energy delivered per kWh of capacity (kWh)4,860.0
Wear cost per kWh delivered0.051440
Charging cost per kWh delivered0.055556
Total cost per kWh delivered0.10700

Open this example in the calculator and change any input.

Formula

\(c_w = \frac{C_b}{N\cdot DoD\cdot f_{avg}}, \quad c = c_w + \frac{c_{ch}}{\eta}\)

Variables

Symbol Meaning SI unit
\(C_b\) Battery pack cost (per kWh of capacity) -
\(N\) Cycle life to end of life -
\(DoD\) Depth of discharge per cycle -
\(f_{avg}\) Average capacity over life (fraction of new) -
\(\eta\) Round-trip efficiency -
\(c_{ch}\) Charging energy price (per kWh) -
\(E_{life}\) Lifetime energy delivered per kWh of capacity (kWh) -
\(c_w\) Wear cost per kWh delivered -
\(c_{ch}/\eta\) Charging cost per kWh delivered -
\(c\) Total cost per kWh delivered -

Method and standards

Battery throughput cost.

Where it is used

  • Battery arbitrage and peak shaving cases.
  • EV and home battery economics.

Common mistakes

  • Using nameplate cycle life at a different DoD.
  • Ignoring capacity fade over life.

Assumptions and limits

  • Cycle ageing only; constant prices.

References

  • Battery throughput cost

Questions and answers

Why does wear cost matter for arbitrage?

Every cycle uses up part of the battery; arbitrage pays only if the price spread exceeds wear cost plus the efficiency loss.

How do LFP and NMC compare?

LFP cells typically last 4,000–8,000 cycles, NMC 1,500–3,000, so LFP has much lower wear cost per kWh for daily cycling.

What do the defaults represent?

An illustrative 250 per kWh pack lasting 6,000 cycles at 90 % depth of discharge, averaging 90 % of new capacity, 90 % round trip and charging at 0.05 per kWh.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Gilbert Masters, Renewable and Efficient Electric Power Systems (Wiley, 2004), ch. 9

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.