Worked example
Example: Illustrative 110 cells, 400 Ah, float. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Number of cells | 110.00 - |
| Rated capacity | 400.00 Ah |
| Gas-producing current per 100 Ah | 1.0000 A |
| Room temperature | 20.000 °C |
| Allowed hydrogen concentration | 1.0000 % |
| Safety factor on gas evolution | 2.0000 - |
| Room volume | 60.000 m³ |
Applying the formula below gives:
| Result | Value |
|---|---|
| Gas-producing current | 4.0000 A |
| Hydrogen evolved | 197.46 L/h |
| Ventilation air flow | 39.491 m³/h |
| Air changes per hour | 0.65819 1/h |
Open this example in the calculator and change any input.
Formula
\(\dot n_{H_2} = \frac{In}{2F}, \quad \dot V_{H_2} = \frac{\dot n_{H_2}RT}{p}, \quad \dot V_a = \frac{s\dot V_{H_2}}{c_{max}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(n\) | Number of cells | - |
| \(C\) | Rated capacity | C |
| \(I_g\) | Gas-producing current per 100 Ah | A |
| \(T\) | Room temperature | K |
| \(c_{max}\) | Allowed hydrogen concentration | - |
| \(s\) | Safety factor on gas evolution | - |
| \(V_r\) | Room volume | m³ |
| \(I\) | Gas-producing current | A |
| \(\dot V_{H_2}\) | Hydrogen evolved | m³/s |
| \(\dot V_a\) | Ventilation air flow | m³/s |
| \(n_{ac}\) | Air changes per hour | 1/s |
Method and standards
Hydrogen ventilation.
Where it is used
- Substation and UPS battery rooms.
- Battery charging areas for forklifts.
Common mistakes
- Using float current for boost charging.
- Placing extract openings low (hydrogen rises).
Assumptions and limits
- All gas current produces hydrogen; ideal gas; well-mixed room.
References
- Faraday's law of hydrogen evolution
Questions and answers
Why does hydrogen form on float charge?
A small overcharge current electrolyses water in vented cells; it rises steeply when boost charging.
Do VRLA batteries need ventilation?
Yes, less, since most gas recombines internally, but some escapes and failures can raise it sharply.
What do the defaults represent?
An illustrative 110-cell, 400 Ah vented battery with 1 A per 100 Ah gas current at 20 °C, kept below 1 % hydrogen with a factor of 2, in a 60 m³ room.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Linden and Reddy, Handbook of Batteries, 4th ed. (McGraw-Hill, 2011)