Worked example
Example: Illustrative 48 V lead-acid cycle. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Charge put in | 105.00 Ah |
| Average charging voltage | 54.500 V |
| Charge taken out | 100.00 Ah |
| Average discharging voltage | 50.500 V |
| Auxiliary consumption over the cycle (BMS, cooling) | 0.10000 kWh |
Applying the formula below gives:
| Result | Value |
|---|---|
| Coulombic efficiency | 95.238 % |
| Voltage efficiency | 92.661 % |
| Energy efficiency (cell) | 88.248 % |
| Round-trip efficiency with auxiliaries | 86.733 % |
| Energy lost per cycle | 0.77250 kWh |
Open this example in the calculator and change any input.
Formula
\(\eta_C = \frac{Q_{out}}{Q_{in}}, \quad \eta_V = \frac{\bar V_{out}}{\bar V_{in}}, \quad \eta_E = \eta_C\eta_V, \quad \eta_{sys} = \frac{E_{out}}{E_{in} + E_{aux}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q_{in}\) | Charge put in | C |
| \(\bar V_{in}\) | Average charging voltage | V |
| \(Q_{out}\) | Charge taken out | C |
| \(\bar V_{out}\) | Average discharging voltage | V |
| \(P_{aux}\) | Auxiliary consumption over the cycle (BMS, cooling) | J |
| \(\eta_C\) | Coulombic efficiency | - |
| \(\eta_V\) | Voltage efficiency | - |
| \(\eta_E\) | Energy efficiency (cell) | - |
| \(\eta_{sys}\) | Round-trip efficiency with auxiliaries | - |
| \(\Delta E\) | Energy lost per cycle | J |
Method and standards
Battery efficiency.
Where it is used
- Storage project performance tests.
- Comparing chemistries for cycling duty.
Common mistakes
- Using coulombic efficiency as energy efficiency.
- Leaving out auxiliary loads.
Assumptions and limits
- One full cycle at a steady state of health.
References
- Battery efficiency definitions
Questions and answers
Why is voltage efficiency below coulombic efficiency in lithium cells?
Charge is near perfect, but internal resistance makes charging voltage higher than discharging voltage.
Why do lead-acid batteries need more charge in?
Gassing and side reactions at the end of charge consume charge, lowering coulombic efficiency.
What do the defaults represent?
An illustrative 48 V lead-acid bank charged with 105 Ah at 54.5 V and discharged 100 Ah at 50.5 V, with 0.1 kWh of auxiliaries.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Linden and Reddy, Handbook of Batteries, 4th ed. (McGraw-Hill, 2011)