Worked example
Example: Illustrative 10 H at 2000 A, half-current. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Coil inductance | 10,000 mH |
| Operating current | 2,000.0 A |
| Minimum current fraction (converter limit) | 50.000 % |
| Discharge power | 2.0000 MW |
Applying the formula below gives:
| Result | Value |
|---|---|
| Energy stored at I_max | 20.000 MJ |
| Usable energy down to I_min | 15.000 MJ |
| Discharge time at P | 7.5000 s |
| Usable energy | 4.1667 kWh |
Open this example in the calculator and change any input.
Formula
\(E = \frac{1}{2}LI^2, \quad E_u = E\left[1 - \left(\frac{I_{min}}{I_{max}}\right)^2\right]\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(L\) | Coil inductance | H |
| \(I_{max}\) | Operating current | A |
| \(I_{min}/I_{max}\) | Minimum current fraction (converter limit) | - |
| \(P\) | Discharge power | W |
| \(E\) | Energy stored at I_max | J |
| \(E_u\) | Usable energy down to I_min | J |
| \(t\) | Discharge time at P | s |
Method and standards
Inductor energy.
Where it is used
- Power quality and pulsed power.
- Comparing short-duration storage.
Common mistakes
- Expecting hours of storage.
- Forgetting the refrigeration load.
Assumptions and limits
- Lossless superconducting coil.
References
- Energy stored in an inductor
Questions and answers
How much energy can a coil store?
Only megajoules for practical sizes, so SMES delivers megawatts for seconds rather than hours.
Why keep a minimum current?
Converters need a minimum coil current to control power; stopping at half current still uses 75 % of the energy.
What do the defaults represent?
An illustrative 10 H coil at 2,000 A, discharged to half current at 2 MW.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Gilbert Masters, Renewable and Efficient Electric Power Systems (Wiley, 2004), ch. 9