Worked example
Example: Illustrative 110 V, 300 Ah, 10 h. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Continuous DC load current | 20.000 A |
| Battery capacity | 300.00 Ah |
| Recharge time | 10.000 h |
| Recharge factor (Ah returned / Ah removed) | 1.1500 - |
| Charging voltage | 123.75 V |
| Charger efficiency | 88.000 % |
| Charger input power factor | 80.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Recharge current | 34.500 A |
| Charger output current | 54.500 A |
| DC output power | 6.7444 kW |
| AC input | 9.5801 kVA |
Open this example in the calculator and change any input.
Formula
\(I = I_L + \frac{kC}{t_r}, \quad S_{ac} = \frac{IV}{\eta\,pf}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(I_L\) | Continuous DC load current | A |
| \(C\) | Battery capacity | C |
| \(t_r\) | Recharge time | s |
| \(k\) | Recharge factor (Ah returned / Ah removed) | - |
| \(V\) | Charging voltage | V |
| \(\eta\) | Charger efficiency | - |
| \(pf\) | Charger input power factor | - |
| \(I_c\) | Recharge current | A |
| \(I\) | Charger output current | A |
| \(P_{dc}\) | DC output power | W |
| \(S_{ac}\) | AC input | VA |
Method and standards
Charger sizing.
Where it is used
- Substation and plant DC systems.
- Telecom and UPS charger selection.
Common mistakes
- Forgetting the standing load.
- Exceeding the battery's maximum charge current.
Assumptions and limits
- Constant-current recharge from full discharge.
References
- Charger sizing for standing load plus recharge
Questions and answers
Why is the recharge factor above 1?
Charging is not 100 % efficient in ampere-hours: lead-acid needs about 10–20 % more Ah back than was taken out.
What charger size do substations use?
Enough to carry the standing load and recharge the battery in 8–12 hours, often with two chargers for redundancy.
What do the defaults represent?
An illustrative 110 V lead-acid system (55 cells at 2.25 V) with 20 A standing load and a 300 Ah battery recharged in 10 hours.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Pansini, Electrical Distribution Engineering, 3rd ed. (Fairmont, 2007)