Worked example
Example: Illustrative 60 kW data room. The inputs, in the units selected above:
| Input | Value |
|---|---|
| IT or critical load | 60.000 kW |
| Efficiency of UPS 1 at this load | 92.000 % |
| Efficiency of UPS 2 at this load | 96.000 % |
| Cooling system COP (0 = no cooling) | 3.0000 - |
| Hours per year | 8,760.0 h |
| Electricity price per kWh | 8.0000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Loss of UPS 1 | 5.2174 kW |
| Loss of UPS 2 | 2.5000 kW |
| Yearly energy (loss plus cooling), UPS 1 | 60.939 MWh |
| Yearly energy (loss plus cooling), UPS 2 | 29.200 MWh |
| Cost saved per year with UPS 2 | 253,913 |
Open this example in the calculator and change any input.
Formula
\(P_L = P\left(\frac1\eta - 1\right), \quad E = P_L\left(1 + \frac1{COP}\right)t\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P\) | IT or critical load | W |
| \(\eta_1\) | Efficiency of UPS 1 at this load | - |
| \(\eta_2\) | Efficiency of UPS 2 at this load | - |
| \(COP\) | Cooling system COP (0 = no cooling) | - |
| \(t\) | Hours per year | s |
| \(c\) | Electricity price per kWh | - |
| \(P_{L1}\) | Loss of UPS 1 | W |
| \(P_{L2}\) | Loss of UPS 2 | W |
| \(E_1\) | Yearly energy (loss plus cooling), UPS 1 | J |
| \(E_2\) | Yearly energy (loss plus cooling), UPS 2 | J |
| \(\Delta C\) | Cost saved per year with UPS 2 | - |
Method and standards
UPS losses.
Where it is used
- Data centres and control rooms.
- UPS replacement decisions.
Common mistakes
- Using full-load efficiency for a lightly loaded UPS.
- Ignoring the cooling energy.
Assumptions and limits
- Constant load and efficiency.
References
- UPS loss and cooling energy balance
Questions and answers
How much does a 4-point better UPS save on 60 kW?
About 2.7 kW of loss and 0.9 kW of cooling: about 32 MWh a year running continuously.
Why include cooling?
Every kW of UPS loss is heat the air conditioning must remove, adding about a third more energy at COP 3.
What do the defaults represent?
An illustrative 60 kW load on a 92 % UPS against a 96 % one, running all year with cooling at COP 3 and 8 per kWh.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.