Worked example
Example: Illustrative 72-cell module at 45 C into 3 ohm. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Short-circuit current | 9.5000 A |
| Open-circuit voltage | 44.000 V |
| Cells in series | 72.000 - |
| Diode ideality factor | 1.2000 - |
| Cell temperature | 45.000 °C |
| Load resistance | 3.0000 Ω |
Applying the formula below gives:
| Result | Value |
|---|---|
| Operating voltage | 28.460 V |
| Operating current | 9.4866 A |
| Power delivered | 0.26998 kW |
| Maximum power of the curve | 0.33341 kW |
| Utilisation of available power | 80.977 % |
| Load resistance for maximum power | 4.1781 Ω |
Open this example in the calculator and change any input.
Formula
\(I = I_{sc} - I_0\left(e^{V/(N_snV_t)} - 1\right), \quad I_0 = \frac{I_{sc}}{e^{V_{oc}/(N_snV_t)} - 1}, \quad I = \frac{V}{R}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(I_{sc}\) | Short-circuit current | A |
| \(V_{oc}\) | Open-circuit voltage | V |
| \(N_s\) | Cells in series | - |
| \(n\) | Diode ideality factor | - |
| \(T_c\) | Cell temperature | K |
| \(R\) | Load resistance | Ω |
| \(V\) | Operating voltage | V |
| \(I\) | Operating current | A |
| \(P\) | Power delivered | W |
| \(P_{mp}\) | Maximum power of the curve | W |
| \(P/P_{mp}\) | Utilisation of available power | - |
| \(R_{mp}\) | Load resistance for maximum power | Ω |
Method and standards
PV and load matching.
Where it is used
- Direct PV water heating and DC motors.
- Teaching maximum power point tracking.
Common mistakes
- Assuming the module always delivers its rated power.
- Ignoring temperature effects on V_oc.
Assumptions and limits
- Ideal diode; uniform irradiance; no series or shunt resistance.
References
- Ideal single-diode PV characteristic and load line
Questions and answers
Why does a direct resistive load waste PV power?
The load line crosses the I-V curve at the maximum power point only at one irradiance; at other light levels the operating point moves away, which is why MPPT controllers exist.
What resistance gives maximum power?
R_mp = V_mp/I_mp at the current irradiance and temperature, about 4–5 Ω for a typical 72-cell module in full sun.
What do the defaults represent?
An illustrative 72-cell module (I_sc 9.5 A, V_oc 44 V) at 45 °C feeding a 3 Ω heating element.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Gilbert Masters, Renewable and Efficient Electric Power Systems (Wiley, 2004), ch. 8