Three-Phase and Single-Phase Power (kW from V, A, PF)

Active, apparent and reactive power from voltage, current and power factor for three-phase or single-phase loads, and the current for a given kW.

Thermal power plantProcess steam and utilitiesElectric motorElectrician and wireman licence examinations

Inputs

Examples: 415 V, 100 A, pf 0.85; current for 75 kWSingle-phase 230 V, 16 A, pf 0.9; current for 2 kW6.6 kV motor 120 A, pf 0.88; current for 1500 kW

Results

Active power1,207.2kW
Apparent power1,371.8kVA
Reactive power651.56kvar
Current for the load entered149.11A

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 415 V, 100 A, pf 0.85; current for 75 kW. The inputs, in the units selected above:

InputValue
SupplyThree-phase (line-to-line voltage)
Voltage415.00 V
Line current100.00 A
Power factor85.000 %
Load for which to find the current75.000 kW

Applying the formula below gives:

ResultValue
Active power61.098 kW
Apparent power71.880 kVA
Reactive power37.865 kvar
Current for the load entered122.75 A

Open this example in the calculator and change any input.

Formula

\(S = k\,V\,I \qquad P = S\cos\varphi \qquad Q = S\sin\varphi \qquad I_r = \frac{P_r}{k\,V\cos\varphi} \qquad k = \sqrt 3 \text{ (three-phase) or } 1\)

Variables

Symbol Meaning SI unit
\(\text{supply}\) three-phase or single-phase –
\(V\) voltage (line-to-line for three-phase) V
\(I\) line current A
\(\cos\varphi\) power factor –
\(P_r\) load for which to find current W
\(P\) active power W
\(S\) apparent power VA
\(Q\) reactive power var
\(I_r\) current for the load A
\(k\) √3 or 1 –

Method and standards

Balanced sinusoidal power definitions (IEC 60050-131).

Where it is used

  • Feeder and motor current estimates.
  • Checking meter readings.
  • Generator and transformer loading.

Common mistakes

  • Using phase voltage with √3.
  • Forgetting power factor.
  • Applying to unbalanced or harmonic-rich loads.

Assumptions and limits

  • Balanced, sinusoidal; harmonics not included.

References

  • IEC 60050-131 (power definitions)

Questions and answers

What power does a 415 V load drawing 100 A at pf 0.85 take?

61.1 kW, 71.9 kVA and 37.9 kvar. A 75 kW load at the same pf draws 122.8 A.

Which voltage do I use for three-phase?

Line-to-line voltage, with √3; with phase voltage use 3 × V × I instead.

Does this include motor efficiency?

No. It is the electrical input; for a motor's shaft output multiply by efficiency.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.