Worked example
Example: 415 V, 100 A, pf 0.85; current for 75 kW. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Supply | Three-phase (line-to-line voltage) |
| Voltage | 415.00 V |
| Line current | 100.00 A |
| Power factor | 85.000 % |
| Load for which to find the current | 75.000 kW |
Applying the formula below gives:
| Result | Value |
|---|---|
| Active power | 61.098 kW |
| Apparent power | 71.880 kVA |
| Reactive power | 37.865 kvar |
| Current for the load entered | 122.75 A |
Open this example in the calculator and change any input.
Formula
\(S = k\,V\,I \qquad P = S\cos\varphi \qquad Q = S\sin\varphi \qquad I_r = \frac{P_r}{k\,V\cos\varphi} \qquad k = \sqrt 3 \text{ (three-phase) or } 1\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\text{supply}\) | three-phase or single-phase | – |
| \(V\) | voltage (line-to-line for three-phase) | V |
| \(I\) | line current | A |
| \(\cos\varphi\) | power factor | – |
| \(P_r\) | load for which to find current | W |
| \(P\) | active power | W |
| \(S\) | apparent power | VA |
| \(Q\) | reactive power | var |
| \(I_r\) | current for the load | A |
| \(k\) | √3 or 1 | – |
Method and standards
Balanced sinusoidal power definitions (IEC 60050-131).
Where it is used
- Feeder and motor current estimates.
- Checking meter readings.
- Generator and transformer loading.
Common mistakes
- Using phase voltage with √3.
- Forgetting power factor.
- Applying to unbalanced or harmonic-rich loads.
Assumptions and limits
- Balanced, sinusoidal; harmonics not included.
References
- IEC 60050-131 (power definitions)
Questions and answers
What power does a 415 V load drawing 100 A at pf 0.85 take?
61.1 kW, 71.9 kVA and 37.9 kvar. A 75 kW load at the same pf draws 122.8 A.
Which voltage do I use for three-phase?
Line-to-line voltage, with √3; with phase voltage use 3 × V × I instead.
Does this include motor efficiency?
No. It is the electrical input; for a motor's shaft output multiply by efficiency.