Short Transmission Line: Regulation and Efficiency

Sending-end voltage, voltage regulation and efficiency of a short overhead line or cable (series R and X only) from receiving-end voltage, load and power factor.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 11 kV, 2 MW at 0.8, 1.5 + j2.5 Ω33 kV, 10 MW at 0.9, 4 + j8 Ω11 kV, 2 MW at 0.8 leading, 1.5 + j2.5 Ω

Results

Short-line model (shunt capacitance neglected): valid up to about 80 km overhead at 50 Hz. Regulation here is (V_S − V_R)/V_R with V_S held.

Line current131.22A
Sending-end line voltage10.952kV
Voltage regulation-0.43937%
Line loss (3 phases)77.479kW
Transmission efficiency96.271%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 11 kV, 2 MW at 0.8, 1.5 + j2.5 Ω. The inputs, in the units selected above:

InputValue
Receiving-end line voltage11.000 kV
Load power2,000.0 kW
Load power factor80.000 %
Power factorLagging (inductive load)
Resistance per phase1.5000 Ω
Reactance per phase2.5000 Ω

Applying the formula below gives:

ResultValue
Line current131.22 A
Sending-end line voltage11.616 kV
Voltage regulation5.6030 %
Line loss (3 phases)77.479 kW
Transmission efficiency96.271 %

Open this example in the calculator and change any input.

Formula

\(\vec V_S = \vec V_R + \vec I(R + jX), \quad \text{Reg} = \frac{|V_S| - |V_R|}{|V_R|}, \quad \eta = \frac{P}{P + 3I^2R}\)

\(\vec I = I(\cos\phi - j\sin\phi), \quad I = \frac{P}{\sqrt3\,V_R\cos\phi}\)

Variables

Symbol Meaning SI unit
\(V_R\) Receiving-end line voltage V
\(P\) Load power W
\(\cos\phi\) Load power factor -
\(\text{pf}\) Lagging or leading power factor -
\(\sin\phi\) Positive for a lagging load, negative for a leading one -
\(R\) Resistance per phase Ω
\(X\) Reactance per phase Ω
\(I\) Line current A
\(V_S\) Sending-end line voltage V
\(\text{Reg}\) Voltage regulation -
\(P_{loss}\) Line loss (3 phases) W
\(\eta\) Transmission efficiency -

Method and standards

Per-phase phasor model.

Where it is used

  • Plant feeders and short lines.
  • Checking voltage at remote loads.

Common mistakes

  • Using line instead of phase quantities.
  • Neglecting reactance on overhead lines.

Assumptions and limits

  • Balanced three-phase; short line.
  • Lagging or leading load: with a leading power factor the regulation can be negative (the receiving-end voltage rises).

References

  • Stevenson and Grainger
  • Power System Analysis (McGraw-Hill, 1994); Kothari and Nagrath
  • Modern Power System Analysis
  • 4th ed. (2011) (short line model)

Questions and answers

Why does lagging power factor worsen regulation?

The reactive current flows through the line reactance and its drop adds in phase with the voltage.

When is the short-line model enough?

For lines under about 80 km, and for most plant feeders and cables at distribution voltages.

What do the defaults represent?

An 11 kV feeder carrying 2 MW at 0.8 power factor through 1.5 + j2.5 Ω per phase.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.