Worked example
Example: 11 kV, 2 MW at 0.8, 1.5 + j2.5 Ω. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Receiving-end line voltage | 11.000 kV |
| Load power | 2,000.0 kW |
| Load power factor | 80.000 % |
| Power factor | Lagging (inductive load) |
| Resistance per phase | 1.5000 Ω |
| Reactance per phase | 2.5000 Ω |
Applying the formula below gives:
| Result | Value |
|---|---|
| Line current | 131.22 A |
| Sending-end line voltage | 11.616 kV |
| Voltage regulation | 5.6030 % |
| Line loss (3 phases) | 77.479 kW |
| Transmission efficiency | 96.271 % |
Open this example in the calculator and change any input.
Formula
\(\vec V_S = \vec V_R + \vec I(R + jX), \quad \text{Reg} = \frac{|V_S| - |V_R|}{|V_R|}, \quad \eta = \frac{P}{P + 3I^2R}\)
\(\vec I = I(\cos\phi - j\sin\phi), \quad I = \frac{P}{\sqrt3\,V_R\cos\phi}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V_R\) | Receiving-end line voltage | V |
| \(P\) | Load power | W |
| \(\cos\phi\) | Load power factor | - |
| \(\text{pf}\) | Lagging or leading power factor | - |
| \(\sin\phi\) | Positive for a lagging load, negative for a leading one | - |
| \(R\) | Resistance per phase | Ω |
| \(X\) | Reactance per phase | Ω |
| \(I\) | Line current | A |
| \(V_S\) | Sending-end line voltage | V |
| \(\text{Reg}\) | Voltage regulation | - |
| \(P_{loss}\) | Line loss (3 phases) | W |
| \(\eta\) | Transmission efficiency | - |
Method and standards
Per-phase phasor model.
Where it is used
- Plant feeders and short lines.
- Checking voltage at remote loads.
Common mistakes
- Using line instead of phase quantities.
- Neglecting reactance on overhead lines.
Assumptions and limits
- Balanced three-phase; short line.
- Lagging or leading load: with a leading power factor the regulation can be negative (the receiving-end voltage rises).
References
- Stevenson and Grainger
- Power System Analysis (McGraw-Hill, 1994); Kothari and Nagrath
- Modern Power System Analysis
- 4th ed. (2011) (short line model)
Questions and answers
Why does lagging power factor worsen regulation?
The reactive current flows through the line reactance and its drop adds in phase with the voltage.
When is the short-line model enough?
For lines under about 80 km, and for most plant feeders and cables at distribution voltages.
What do the defaults represent?
An 11 kV feeder carrying 2 MW at 0.8 power factor through 1.5 + j2.5 Ω per phase.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.