Power Factor Correction Capacitor (kvar)

Capacitor kvar needed to raise the power factor of a load, with kVA and line current before and after and the reduction in line losses.

Thermal power plantProcess steam and utilitiesElectric motorElectrician and wireman licence examinations

Inputs

Examples: Plant 500 kW, 0.75 to 0.95, 415 VMotor 90 kW input, 0.82 to 0.98, 415 VHT load 2 MW, 0.85 to 0.99, 11 kV

Results

Capacitor rating required276.62kvar
Reactive power before440.96kvar
Reactive power after164.34kvar
Apparent power before666.67kVA
Apparent power after526.32kVA
Line current before927.47A
Line current after732.21A
Reduction of line losses (I² R)37.673%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Plant 500 kW, 0.75 to 0.95, 415 V. The inputs, in the units selected above:

InputValue
Active power of the load500.00 kW
Present power factor0.75000 -
Target power factor0.95000 -
Line-to-line voltage (three-phase)415.00 V

Applying the formula below gives:

ResultValue
Capacitor rating required276.62 kvar
Reactive power before440.96 kvar
Reactive power after164.34 kvar
Apparent power before666.67 kVA
Apparent power after526.32 kVA
Line current before927.47 A
Line current after732.21 A
Reduction of line losses (I² R)37.673 %

Open this example in the calculator and change any input.

Formula

\(Q_c = P\,(\tan\varphi_1 - \tan\varphi_2) \qquad Q_1 = P\tan\varphi_1 \qquad Q_2 = P\tan\varphi_2\)

\(S_1 = \frac{P}{\cos\varphi_1} \qquad S_2 = \frac{P}{\cos\varphi_2} \qquad I = \frac{S}{\sqrt 3\,U} \qquad \Delta P_{loss} = 1 - \left(\frac{\cos\varphi_1}{\cos\varphi_2}\right)^2\)

Variables

Symbol Meaning SI unit
\(P\) active power of the load W
\(\cos\varphi_1\) present power factor –
\(\cos\varphi_2\) target power factor –
\(U\) line-to-line voltage V
\(Q_c\) capacitor rating required var
\(Q_1\) reactive power before var
\(Q_2\) reactive power after var
\(S_1\) apparent power before VA
\(S_2\) apparent power after VA
\(I_1\) line current before A
\(I_2\) line current after A
\(\Delta P_{loss}\) relative reduction of the I²R losses upstream –

Method and standards

The power triangle for a balanced three-phase load: active power is unchanged, the capacitor supplies the difference in reactive power. Capacitor ratings and duty are covered by IEC 60831-1.

Where it is used

  • Sizing capacitor banks for plants and motors.
  • Reducing demand charges and cable losses.
  • Checking an existing bank after load changes.

Common mistakes

  • Overcorrecting at light load.
  • Ignoring harmonics from variable speed drives.
  • Correcting a motor beyond its no-load magnetising current.

Assumptions and limits

  • Sinusoidal voltage and current; harmonics need detuned banks and a separate study.
  • Capacitor output is rated at its rated voltage; at a lower voltage it delivers (U/U_r)² of its rating.
  • Losses are those upstream of the capacitor; the capacitor itself has small losses not included.

References

  • IEC 60831-1 (shunt power capacitors, context); power triangle definitions

Questions and answers

How many kvar do I need to correct the power factor?

Q_c = P·(tanφ₁ − tanφ₂). A 500 kW load at 0.75 needs 277 kvar to reach 0.95; its current at 415 V falls from 927 A to 732 A.

How much do losses fall?

Line losses go with the square of the current, so they fall by 1 − (cosφ₁/cosφ₂)². From 0.75 to 0.95 that is 38 % of the losses upstream of the capacitor.

Why not correct to 1.0?

At light load a fixed bank sized for unity over-corrects and raises the voltage, and a bank near resonance amplifies harmonics. Most designs aim at 0.95–0.98 with automatic (APFC) steps and detuning reactors where harmonics exist.

Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.