Neutral Current in an Unbalanced Three-Phase System

Neutral current of a three-phase four-wire system from the three phase currents at the same power factor, with the average current and the unbalance.

Thermal power plantProcess steam and utilities

Inputs

Examples: 100, 80 and 60 ABalanced 50 AOne phase only, 40 A

Results

Fundamental currents 120° apart at one power factor. Third-harmonic currents from electronic loads add in the neutral and are not included.

Neutral current0A
Average phase current50.000A
Current unbalance (largest deviation from the average)0%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 100, 80 and 60 A. The inputs, in the units selected above:

InputValue
Current in phase A100.00 A
Current in phase B80.000 A
Current in phase C60.000 A

Applying the formula below gives:

ResultValue
Neutral current34.641 A
Average phase current80.000 A
Current unbalance (largest deviation from the average)25.000 %

Open this example in the calculator and change any input.

Formula

\(I_N = \sqrt{I_a^2 + I_b^2 + I_c^2 - I_a I_b - I_b I_c - I_c I_a}\)

Variables

Symbol Meaning SI unit
\(I_a\) Current in phase A A
\(I_b\) Current in phase B A
\(I_c\) Current in phase C A
\(I_N\) Neutral current A
\(I_{avg}\) Average phase current A
\(u\) Current unbalance (largest deviation from the average) -

Method and standards

Magnitude of the sum of three phasors 120° apart.

Where it is used

  • Checking neutral loading in distribution boards.
  • Balancing single-phase loads.

Common mistakes

  • Adding the currents arithmetically.
  • Ignoring harmonics.

Assumptions and limits

  • Same power factor in each phase (each current at the same angle to its phase voltage); fundamental only. Different power factors per phase change the phasor angles and so the neutral current: add the currents as phasors in that case.

References

  • Phasor sum of three currents 120° apart

Questions and answers

What is the neutral current for 100, 80 and 60 A?

34.6 A.

When is it zero?

When the three currents are equal and free of triplen harmonics.

Why can the neutral carry more than a phase?

Third harmonics from computers and LED drivers add up in the neutral.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.