Worked example
Example: 100, 80 and 60 A. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Current in phase A | 100.00 A |
| Current in phase B | 80.000 A |
| Current in phase C | 60.000 A |
Applying the formula below gives:
| Result | Value |
|---|---|
| Neutral current | 34.641 A |
| Average phase current | 80.000 A |
| Current unbalance (largest deviation from the average) | 25.000 % |
Open this example in the calculator and change any input.
Formula
\(I_N = \sqrt{I_a^2 + I_b^2 + I_c^2 - I_a I_b - I_b I_c - I_c I_a}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(I_a\) | Current in phase A | A |
| \(I_b\) | Current in phase B | A |
| \(I_c\) | Current in phase C | A |
| \(I_N\) | Neutral current | A |
| \(I_{avg}\) | Average phase current | A |
| \(u\) | Current unbalance (largest deviation from the average) | - |
Method and standards
Magnitude of the sum of three phasors 120° apart.
Where it is used
- Checking neutral loading in distribution boards.
- Balancing single-phase loads.
Common mistakes
- Adding the currents arithmetically.
- Ignoring harmonics.
Assumptions and limits
- Same power factor in each phase (each current at the same angle to its phase voltage); fundamental only. Different power factors per phase change the phasor angles and so the neutral current: add the currents as phasors in that case.
References
- Phasor sum of three currents 120° apart
Questions and answers
What is the neutral current for 100, 80 and 60 A?
34.6 A.
When is it zero?
When the three currents are equal and free of triplen harmonics.
Why can the neutral carry more than a phase?
Third harmonics from computers and LED drivers add up in the neutral.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.