Distribution Line I²R Loss and Energy Lost

Power lost in a feeder or distribution line from current, resistance per km and length, as a share of the power carried, with the energy lost in a year.

Thermal power plantProcess steam and utilities

Inputs

Examples: 200 A, 0.1 Ω/km, 500 m, three phase 415 V32 A, 1.15 Ω/km, 60 m, single phase 230 V150 A, 0.2 Ω/km, 3 km, 11 kV

Results

Power lost in the line40.500kW
Power carried2,572.1kW
Loss as a share of the power carried1.5746%
Energy lost in the year324,000kWh

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 200 A, 0.1 Ω/km, 500 m, three phase 415 V. The inputs, in the units selected above:

InputValue
Line current200.00 A
Resistance of one conductor per unit length0.10000 Ω/km
Route length500.00 m
SupplyThree phase
Voltage (line to line for three phase)415.00 V
Power factor0.90000 -
Running time in the year6,000.0 h

Applying the formula below gives:

ResultValue
Power lost in the line6.0000 kW
Power carried129.38 kW
Loss as a share of the power carried4.6374 %
Energy lost in the year36,000 kWh

Open this example in the calculator and change any input.

Formula

\(P_{loss} = 3\, I^2\, r\, L\ (3\phi), \quad 2\, I^2\, r\, L\ (1\phi)\)

\(E_{loss} = P_{loss}\, t\)

Variables

Symbol Meaning SI unit
\(I\) Line current A
\(r\) Resistance of one conductor per unit length Ω/m
\(L\) Route length m
\(\text{phases}\) Supply -
\(V\) Voltage (line to line for three phase) V
\(\cos\varphi\) Power factor -
\(t\) Running time in the year s
\(P_{loss}\) Power lost in the line W
\(P\) Power carried W
\(p_{loss}\) Loss as a share of the power carried -
\(E_{loss}\) Energy lost in the year J

Method and standards

Joule heating in each loaded conductor.

Where it is used

  • Energy audits of distribution systems.
  • Justifying a larger cable or correction.

Common mistakes

  • Counting only one conductor.
  • Using 20 °C resistance for a hot cable.

Assumptions and limits

  • Balanced load; neutral unloaded.
  • The annual energy assumes the same current for all the running hours; for a varying load multiply by the loss-load factor (mean of I² over peak I²) instead.

References

  • Joule's law: 3 I² R (three phase)
  • 2 I² R (single phase, go and return)

Questions and answers

What does 200 A lose over 500 m of 0.1 Ω/km cable, three phase?

6.0 kW, which over 6000 h is 36000 kWh.

How does power factor help?

Loss goes with current squared; raising the power factor from 0.8 to 0.95 cuts the loss by 29 %.

Which resistance?

At the operating temperature; hot conductors have about 20 % more than at 20 °C.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.