Worked example
Example: 100 kVA at 415 V three phase; 100 A. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Apparent power | 100.00 kVA |
| Voltage (line to line for three phase) | 415.00 V |
| Supply | Three phase |
| Current (to find kVA) | 100.00 A |
Applying the formula below gives:
| Result | Value |
|---|---|
| Current for the kVA given | 139.12 A |
| Apparent power for the current given | 71.880 kVA |
Open this example in the calculator and change any input.
Formula
\(I = \frac{S}{\sqrt 3\, V}\ (3\phi), \quad I = \frac{S}{V}\ (1\phi)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(S\) | Apparent power | VA |
| \(V\) | Voltage (line to line for three phase) | V |
| \(\text{phases}\) | Supply | - |
| \(I_{given}\) | Current (to find kVA) | A |
| \(I\) | Current for the kVA given | A |
| \(S_I\) | Apparent power for the current given | VA |
Method and standards
Definition of apparent power.
Where it is used
- Generator, transformer and UPS ratings.
- Cable and breaker selection from a kVA figure.
Common mistakes
- Using phase voltage with √3.
- Confusing kVA with kW.
Assumptions and limits
- Balanced three-phase load.
References
- AC power relations S = V I (1φ)
- S = √3 V I (3φ)
Questions and answers
How many amps is 100 kVA at 415 V three phase?
139.1 A: I = S / (√3 V).
And single phase at 230 V?
434.8 A: I = S / V.
Does power factor matter?
Not for kVA to amps. It matters when converting kW to amps.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.