FireCADCalc

Capacitor kvar to Microfarad Calculator (Single and Three Phase)

Capacitance in microfarads for a capacitor of given kvar at a voltage and frequency, single phase or three phase in delta or star, with current and reactance.

Thermal power plantProcess steam and utilitiesElectrician and wireman licence examinations

Inputs

Examples: 25 kvar, 415 V, 50 Hz, delta25 kvar, 415 V, 50 Hz, star2 kvar, 230 V, 50 Hz, single phase

Results

Capacitance of each element (per phase)462.06µF
Line current34.780A
Reactance of each element6.8890Ω

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 25 kvar, 415 V, 50 Hz, delta. The inputs, in the units selected above:

InputValue
Reactive power of the bank25.000 kvar
Voltage (line to line for three phase)415.00 V
Frequency50.000 Hz
ConnectionThree phase, delta

Applying the formula below gives:

ResultValue
Capacitance of each element (per phase)154.02 µF
Line current34.780 A
Reactance of each element20.667 Ω

Open this example in the calculator and change any input.

Formula

\(C_\Delta = \frac{Q}{3\, \omega\, V^2}, \quad C_Y = \frac{Q}{\omega\, V^2}, \quad C_{1\phi} = \frac{Q}{\omega\, V^2}, \quad \omega = 2\pi f\)

Variables

Symbol Meaning SI unit
\(Q\) Reactive power of the bank var
\(V\) Voltage (line to line for three phase) V
\(f\) Frequency 1/s
\(\text{conn}\) Connection -
\(C\) Capacitance of each element (per phase) F
\(I\) Line current A
\(X_C\) Reactance of each element Ω

Method and standards

Reactive power of a capacitor, Q = V²/X_C per element.

Where it is used

  • Checking capacitor units with a capacitance meter.
  • Replacing failed elements.

Common mistakes

  • Mixing line and phase voltage.
  • Forgetting the 3 for delta.

Assumptions and limits

  • Ideal capacitors; rated voltage and frequency.

References

  • Q = ω C V² per element (AC circuit theory)

Questions and answers

How many µF per phase is a 25 kvar, 415 V delta bank at 50 Hz?

154 µF per phase, drawing 34.8 A.

Why is a star bank three times the µF?

Each star element sees only V/√3, so it needs three times the capacitance for the same kvar.

Does frequency matter?

Yes: kvar is proportional to frequency.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators