Worked example
Example: 25 kvar, 415 V, 50 Hz, delta. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Reactive power of the bank | 25.000 kvar |
| Voltage (line to line for three phase) | 415.00 V |
| Frequency | 50.000 Hz |
| Connection | Three phase, delta |
Applying the formula below gives:
| Result | Value |
|---|---|
| Capacitance of each element (per phase) | 154.02 µF |
| Line current | 34.780 A |
| Reactance of each element | 20.667 Ω |
Open this example in the calculator and change any input.
Formula
\(C_\Delta = \frac{Q}{3\, \omega\, V^2}, \quad C_Y = \frac{Q}{\omega\, V^2}, \quad C_{1\phi} = \frac{Q}{\omega\, V^2}, \quad \omega = 2\pi f\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q\) | Reactive power of the bank | var |
| \(V\) | Voltage (line to line for three phase) | V |
| \(f\) | Frequency | 1/s |
| \(\text{conn}\) | Connection | - |
| \(C\) | Capacitance of each element (per phase) | F |
| \(I\) | Line current | A |
| \(X_C\) | Reactance of each element | Ω |
Method and standards
Reactive power of a capacitor, Q = V²/X_C per element.
Where it is used
- Checking capacitor units with a capacitance meter.
- Replacing failed elements.
Common mistakes
- Mixing line and phase voltage.
- Forgetting the 3 for delta.
Assumptions and limits
- Ideal capacitors; rated voltage and frequency.
References
- Q = ω C V² per element (AC circuit theory)
Questions and answers
How many µF per phase is a 25 kvar, 415 V delta bank at 50 Hz?
154 µF per phase, drawing 34.8 A.
Why is a star bank three times the µF?
Each star element sees only V/√3, so it needs three times the capacitance for the same kvar.
Does frequency matter?
Yes: kvar is proportional to frequency.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.