Alternator EMF Equation and Frequency

Generated EMF per phase and line voltage of a three-phase alternator from flux per pole, turns per phase, pitch and distribution factors, with the frequency.

Thermal power plantProcess steam and utilities

Inputs

Examples: 4 poles, 1 500 rpm, 30 mWb, 40 turns16 poles, 375 rpm, 50 mWb, 120 turns2 poles, 3 600 rpm, 1.2 Wb, 12 turns

Results

Frequency P N / 250.000Hz
EMF per phase247.21V
Line voltage, star connected428.18V
Winding factor k_p k_d0.92736

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 4 poles, 1 500 rpm, 30 mWb, 40 turns. The inputs, in the units selected above:

InputValue
Number of poles4.0000 -
Speed1,500.0 rpm
Flux per pole30.000 mWb
Turns in series per phase40.000 -
Pitch factor0.96600 -
Distribution factor0.96000 -

Applying the formula below gives:

ResultValue
Frequency P N / 250.000 Hz
EMF per phase247.21 V
Line voltage, star connected428.18 V
Winding factor k_p k_d0.92736

Open this example in the calculator and change any input.

Formula

\(f = \frac{P N}{2}, \quad E_{ph} = \sqrt 2\, \pi\, k_p k_d f \Phi T_{ph} \approx 4.44\, k_p k_d f \Phi T_{ph}\)

Variables

Symbol Meaning SI unit
\(P\) Number of poles -
\(N\) Speed 1/s
\(\Phi\) Flux per pole Wb
\(T_{ph}\) Turns in series per phase -
\(k_p\) Pitch factor -
\(k_d\) Distribution factor -
\(f\) Frequency P N / 2 1/s
\(E_{ph}\) EMF per phase V
\(E_L\) Line voltage, star connected V
\(k_w\) Winding factor k_p k_d -

Method and standards

RMS EMF of a distributed, short-pitched winding.

Where it is used

  • Electrical examinations.
  • Generator rewinding checks.

Common mistakes

  • Using conductors as turns.
  • Speed in rpm in f = PN/2.

Assumptions and limits

  • Sinusoidal flux distribution.
  • The number of poles must be an even whole number.

References

  • Synchronous machine EMF equation E_ph = √2 π k_p k_d f Φ T_ph (textbook)

Questions and answers

What EMF for 4 poles, 1500 rpm, 30 mWb, 40 turns, k_p 0.966, k_d 0.96?

50 Hz; 247.2 V per phase, 428.2 V line.

Turns or conductors?

Turns per phase T = Z/2, where Z is the conductors in series per phase.

Why short-pitch the coils?

It lowers the EMF a little but removes harmonics.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.